8.7 Programming
The device is programmed in the menu mode.
In menu mode, the joystick button can be used to navigate easily and intuitively between the main menu,
submenu and parameter menu.
Call up main menu: Press and hold the joystick button
↓
for 2 s (starting from a display page)
Back to display pages: Briefly press the joystick button
←
(starting from the main menu)
Below is the menu structure with descriptions of the parameters
Main Menu
Submenu
Parameter menu
Parameter description
Programs
Select the program you want using the
↓
/
↑
keys and
confirm by pressing
→
. Then select between the
options "set" and "change voltage" (rated voltage) and
set the program by pressing 2x
→
(rated voltage is
requested after the program change if necessary).
Mains connect
Mains connection
Connection
These parameters are permanently stored in the
program
and cannot be changed. Exception: Rated voltage
when changing a program
Nominal voltage
Coupling device
Switch on condi
Voltage
Active
Connection conditions:
The limit values for these parameters must be met after
the device has been started so that the K1 and K2
relays can switch on after the switch-on delay has
elapsed
Switch on
U max.
condition
U min.
Frequency
Active
F max.
F min.
Switch on delay
Time
After alarms
Switch back
activated: Device switches on again as soon as the
"alarm off" value of the activated alarm is reached
all f + U < + U <<: Device switches on again as soon as
all "Alarm off" values of the frequency alarms and
voltage alarms U <, U << are reached
Short alarm
Active
Only visible in program Pr1.01 and Pr1.07:
For short alarms a shorter reset time can be realized
only in Pr1.01 and
Pr1.07
Alarm time
Reset time
Voltage
U >> 59>S2
Alarm active
Voltage alarms:
Alarm on
•
U >> (larger larger)
Alarm off
•
U > (larger)
Delay alarm on
•
U 10 minutes mean value
Delay alarm off
•
U < (smaller)
U > 59>S1
Alarm active
•
U << (smaller smaller)
Alarm on
•
U0 (zero voltage)
Alarm off
Delay alarm on
Delay alarm off
Parameter:
UM> 59-Av 10Min Alarm active
•
Alarm active
yes / no
Alarm on
•
Alarm on
limit value Alarm on
Alarm off
•
Alarm off
limit value Alarm off
Delayed Alarm on
•
Delay Alarm on Alarm for this period is
delayed
Delayed Alarm off
U < 27<S1
Alarm active
•
Delay Alarm off Alarm off for this period is
delayed
Alarm on
Alarm off
Delay alarm on
Delay alarm off