9
Hand held terminal A-G-247NW
In the ECblue BASIC-MODBUS version, a direct connection is possible, with ECblue BASIC it is via
the AM-MODBUS auxiliary module.
The connection is made by a 4-wire cable at the terminals: A (D+), B (D-) and GND. E. g. telephone
cable type: J-Y (St) Y 2x2x0.6 (or similar), maximum cable length approx. 250 m.
The voltage supply of the terminal is made by the accumulators inserted there or the plug power
supply unit.
Connection terminal type A-G-247NW for service
13.05.2013
v_a-g-247nw_at_ecblue.vsd
GND
A
(D+)
B
(D-)
A-G-247NW
ECblue
Information
•
Programming of the ECblue BASIC-MODBUS version using the A-G-247NW hand held terminal is
described below. Programming of the ECblue BASIC version depends on the optional auxiliary
modules. For further details, refer to the operating instructions for the module used.
•
When programming using the "ZAset Mobile" app, the parameters are displayed in a different way.
9.1
Menu group Setting
Attention!
The fans and motors for which these assembly instructions are valid have a
“
100% function
”
in which
operation at full speed is possible in case of failure of the setting signal. It is selected by activating the
setting
“
Set Intern 2
”
(factory setting 100 %) via the digital input.
When using the
“
100% function
”
changes to the
“
Set Intern 2
”
and
“
Max. Speed
”
parameters
are not allowed.
Setting
Set Internal1
Setting only in Controlmode
|
4
|
active (see Controller Setup).
Via the inputs
“
D1
”
/
“
E1
”
it is possible to switch to
“
Default Internal2
”
or
“
Default
Internal3
”
(see IO Setup).
Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Set Internal2
Setting only in control mode
|
5
|
active only in control mode
|
4
|
, if activated via inputs
“
D1
”
/
“
E1
”
(see Controller Setup / IO Setup).
Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Set Internal3
Setting only in control mode
|
6
|
active only in control mode
|
4
|
, if activated via inputs
“
D1
”
/
“
E1
”
(see Controller Setup / IO Setup).
Setting range manual speed setting: 0...100 % (Rated speed)
Factory setting*: 100 % (Rated speed)
Min. Speed
The basic speed is active in every control mode.
Setting range: 0...100 % (Rated speed)
Factory setting*: 0 %
Assembly instructions
ECblue BASIC-MODBUS, ECblue BASIC
Hand held terminal A-G-247NW
L-BAL-F079D-GB 2044 Index 002
Part.-No.
49/80