![ZIEHL-ABEGG ECblue BASIC-MODBUS Скачать руководство пользователя страница 20](http://html2.mh-extra.com/html/ziehl-abegg/ecblue-basic-modbus/ecblue-basic-modbus_assembly-instructions-manual_3691239020.webp)
1
8
1
9/10
4
5
7
6
3
ai_kl_1905_1
fi
gure 2
fi
gure 3
Feed the fan (1) into the chimney in accordance with
fi
g. 3
, and center it in the mounting bracket (4).
In addition, the support is to be secured in accordance with
fi
g. 2
by using bolts (9/10).
The four support clamps (5) are used as support eyelets for additional
fi
xings (e.g. by standing ropes)
in order to relieve the chimney of the weight of greater fans.
Installation kit (Part.-No. 00370979 / 00372782)
Pos.
Designation
Piece
1
Axial fan
-
3
Chimney
-
4
Mounting bracket
4
5
Support bracket
4
6
M8x70 screws EN ISO 4014
8
7
M8 nuts EN ISO 10511 self-locking
8
7a
8.4 washer EN ISO 7089
8
8
Protective cap
4
9
Screw M8x30 EN ISO 4017 / screw M8x25 EN ISO4017
4
10
M8 nuts EN ISO 10 511 self-locking
4
10a
8.4 washer EN ISO 7089
4
All fastening elements made of stainless steel
4.9
ZAplus fans
When mounting ZAplus fans, ensure plastic-compliant connectors.
Recommended tightening torques M
A
when using
fl
at fastening discs according to EN ISO 7089 or DIN125
ZAplus size ((tye: ZC.., ZN.., ZF..)
040
045 - 063
> 071
Thread size
M8
M10
M12
Property class 8.8, friction coefcient
µ
ges = 0.12
12 Nm
24 Nm
40 Nm
Tightening torque guard grille
fi
tting: 6 Nm
Information
•
Since the concrete bolt or screw varies by customer unit, these recommendations must be checked
for each respective situation.
•
Secure the cable covering against loss after connecting the motor by securing with 2 cable ties.
•
For a version with a square rear wall (design Q), removal of this square plastic plate is prohibited.
Assembly instructions
ECblue BASIC-MODBUS, ECblue BASIC
Mounting
L-BAL-F079D-GB 2044 Index 002
Part.-No.
20/80