PREMIER AD INSTALLATION MANUAL.
Software:31/3/04 & LC6
Approved Document No: GLT.MAN-105
PAGE 4
Issue : 1.02 Authorised: GH Date: 15/03/2004
2. LIST OF COMPATIBLE EQUIPMENT
Stock No
Product Code
Device
37-150
PR-AD
Premier AD Fire Alarm Panel
37-155
PREP-AD
Premier AD Repeater
80-110
FEAI2000
Fyreye Addressable Ionisation Detector
80-120
FEAO2000
Fyreye Addressable Optical Detector
80-130
FEAH2000
Fyreye Addressable Heat Detector
80-131
FEAHH2000
Fyreye Addressable High Temperature Heat Detector
80-140
FEAOH2000
Fyreye Addressable Multi-Point Detector
80-150
FECO2000
Fyreye Addressable Carbon Monoxide Detector
80-050 FE-CB
Fyreye
Common
Base
80-080
FEA-RB
Fyreye Addressable Relay Base
80-090
FE-IB
Fyreye Addressable Loop Isolator Base
80-100
FEA-SB
Fyreye Addressable Sounder Base
80-101
FEA-ISB
Fyreye Addressable Isolator Sounder Base
43-001
ZT-MCP/AD
Zeta Addressable Call Point
43-022
ZT-MCP/AD/WP
Zeta Weatherproof Addressable Call Point
48-100 ZIU
Zeta
Input
Unit
48-105
ZIOU
Zeta Input Output Unit
48-110
ZSCC
Zeta Sounder Control Module
48-115
ZT-ZM
Zeta Zone Monitor Unit
42-007
ZAMT
Zeta Addressable Maxitone Sounder
42-008
ZAMD
Zeta Addressable Miditone Sounder
42-030
ZAST
Zeta Addressable Securetone Sounder
48-020
ZTA/LE2
Zeta Addressable Remote Led Indicator
47-055
ZTA-FR50
Fyreye Addressable Reflective Beam Detector 50m
47-056
ZTA-FR100
Fyreye Addressable Reflective Beam Detector 100m
47-110
FE+50/AD
Fyreye Plus Addressable Aspiration Detector
42-001
ZMT/8
Zeta Conventional Maxitone Sounder
42-002
ZMD/8
Zeta Conventional Miditone Sounder
42-004
ZST/8
Zeta Conventional Securetone Sounder
42-005
ZIDC/10R
Zeta Conventional Megatone Sounder
42-011
ZFL2RR
Zeta Conventional Flasher
42-013
ZLT/8RR
Zeta Conventional Flasher Sounder
41-003
ZTB6B/24
Zeta Conventional 6” Bells
41-005
ZTB8B
Zeta Conventional 8” Bells
2.1 SUPPORTED SOUNDER TYPES & THEIR APPLICATIONS
The Premier AD supports 4 general sounder types; conventional, addressable, addressable sounder controller,
and associated sounders. All types have advantages & disadvantages.
Sounder type
Advantage
Disadvantage
Conventional
Wide range of devices
Devices tend to be cheaper.
Immediate start / stop
No quiescent current
Needs extra cabling
Always configured as common sounders
Addressable
No Extra Cabling
Sounders can be configured as zonal
Tends to be more expensive
Maximum 32 per loop for quick start/stop
Quiescent current high
Uses device address.
Associated
(sounder-
base)
No Extra Cabling
Doesn’t occupy Device Address
Can have more than 32 per loop
4-8 second start & stop time.
Always configured as common sounders
Needs detector present to operate.
Does not operate during sounder test mode
Addressable
Sounder
Circuit
Controller
Wide range of devices
Devices tend to be cheaper.
Can add many sounder circuits to system
Sounder circuit can be set as zonal
Needs Extra Cabling.
Needs External PSU
Maximum 32 per loop for quick start/stop
Quiescent current high
Uses device address.