PREMIER AD INSTALLATION MANUAL.  

 

 

Software:31/3/04 & LC6 

 

 

 

Approved Document No: GLT.MAN-105

 

 

 

 

PAGE 4

 

Issue : 1.02         Authorised: GH      Date: 15/03/2004

 

 

2. LIST OF COMPATIBLE EQUIPMENT 

 

Stock No 

Product Code 

Device 

 

 

 

 

 

37-150 

PR-AD 

Premier AD Fire Alarm Panel 

 

37-155 

PREP-AD 

Premier AD Repeater 

 

 

 

 

 

80-110 

FEAI2000 

Fyreye Addressable Ionisation Detector 

 

80-120 

FEAO2000 

Fyreye Addressable Optical Detector 

 

80-130 

FEAH2000 

Fyreye Addressable Heat Detector 

 

80-131 

FEAHH2000 

Fyreye Addressable High Temperature Heat Detector 

 

80-140 

FEAOH2000 

Fyreye Addressable Multi-Point Detector 

 

80-150 

FECO2000 

Fyreye Addressable Carbon Monoxide Detector 

 

 

 

 

 

80-050 FE-CB 

Fyreye 

Common 

Base 

 

80-080 

FEA-RB 

Fyreye Addressable Relay Base 

 

80-090 

FE-IB 

Fyreye Addressable Loop Isolator Base 

 

80-100 

FEA-SB 

Fyreye Addressable Sounder Base 

 

80-101 

FEA-ISB 

Fyreye Addressable Isolator Sounder Base 

 

 

 

 

 

43-001 

ZT-MCP/AD 

Zeta Addressable Call Point 

 

43-022 

ZT-MCP/AD/WP 

Zeta Weatherproof Addressable Call Point 

 

 

 

 

 

48-100 ZIU 

Zeta 

Input 

Unit 

 

48-105 

ZIOU 

Zeta Input Output Unit 

 

48-110 

ZSCC 

Zeta Sounder Control Module 

 

48-115 

ZT-ZM 

Zeta Zone Monitor Unit 

 

 

 

 

 

42-007 

ZAMT 

Zeta Addressable Maxitone Sounder 

 

42-008 

ZAMD 

Zeta Addressable Miditone Sounder 

 

42-030 

ZAST 

Zeta Addressable Securetone Sounder 

 

48-020 

ZTA/LE2 

Zeta Addressable Remote Led Indicator 

 

 

 

 

 

47-055 

ZTA-FR50 

Fyreye Addressable Reflective Beam Detector 50m  

 

47-056 

ZTA-FR100 

Fyreye Addressable Reflective Beam Detector 100m 

 

47-110 

FE+50/AD 

Fyreye Plus Addressable Aspiration Detector 

 

 

 

 

 

42-001 

ZMT/8 

Zeta Conventional Maxitone Sounder 

 

42-002 

ZMD/8 

Zeta Conventional Miditone Sounder 

 

42-004 

ZST/8 

Zeta Conventional Securetone Sounder 

 

42-005 

ZIDC/10R 

Zeta Conventional Megatone Sounder 

 

42-011 

ZFL2RR 

Zeta Conventional Flasher  

 

42-013 

ZLT/8RR 

Zeta Conventional Flasher Sounder 

 

41-003 

ZTB6B/24 

Zeta Conventional 6” Bells 

 

41-005 

ZTB8B 

Zeta Conventional 8” Bells 

 

 

 

 

 

 

 

 
 

 

2.1 SUPPORTED SOUNDER TYPES & THEIR APPLICATIONS  

 

The Premier AD supports 4 general sounder types; conventional, addressable, addressable sounder controller, 
and associated sounders. All types have advantages & disadvantages. 

 

Sounder type 

Advantage 

Disadvantage 

Conventional 

Wide range of devices 
Devices tend to be cheaper. 
Immediate start / stop 
No quiescent current 

Needs extra cabling 
Always configured as common sounders 

Addressable 

No Extra Cabling 
Sounders can be configured as zonal 

Tends to be more expensive 
Maximum 32 per loop for quick start/stop 
Quiescent current high 
Uses device address. 

Associated 
(sounder-
base) 

No Extra Cabling 
Doesn’t occupy Device Address 
Can have more than 32 per loop 

4-8 second start & stop time. 
Always configured as common sounders 
Needs detector present to operate. 
Does not operate during sounder test mode 

Addressable 
Sounder 
Circuit 
Controller 

Wide range of devices 
Devices tend to be cheaper. 
Can add many sounder circuits to system 
Sounder circuit can be set as zonal 

Needs Extra Cabling. 
Needs External PSU 
Maximum 32 per loop for quick start/stop 
Quiescent current high 
Uses device address. 

Содержание NPAD

Страница 1: ...INSTALLATION MANUAL...

Страница 2: ...CABLE ENTRY 5 2 FIXING THE BACKBOX TO THE WALL 6 CONNECTING MAINS BATTERY POWER 12 6 1 CONNECTING MAINS POWER 6 2 CONNECTING THE BATTERIES 7 FIELD DEVICE TERMINATION 13 7 1 TERMINATING THE DETECTION A...

Страница 3: ...nal 1 1 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device If you are not familiar with binary check the table on page 17 o...

Страница 4: ...Reflective Beam Detector 100m 47 110 FE 50 AD Fyreye Plus Addressable Aspiration Detector 42 001 ZMT 8 Zeta Conventional Maxitone Sounder 42 002 ZMD 8 Zeta Conventional Miditone Sounder 42 004 ZST 8...

Страница 5: ...t person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer con...

Страница 6: ...e screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this...

Страница 7: ...are permitted on the loop There is no limit loop load permitting to the number of sounder bases that can be connected to a loop On the Premier AD Panel all Sounder Bases are always configured as commo...

Страница 8: ...C LOOP IN LOOP OUT LOOP IN LOOP OUT RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals a...

Страница 9: ...5W LOOP IN LOOP OUT LOOP IN LOOP OUT Zeta Sounder Controller Circuit ZSCC 48 110 24 Volt Supply LOOP IN LOOP OUT LOOP IN LOOP OUT 47K End of Line Resistor Zeta Input Output Unit ZIOU 48 105 47K EOL 0...

Страница 10: ...local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Fault Output FAULT This Output is energised in the quiescent condition In a fault condition...

Страница 11: ...f a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via on...

Страница 12: ...ference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOL...

Страница 13: ...Y Brass Glands Figure 6 Detector and Sounder Circuit Connection 7 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on th...

Страница 14: ...the example above zone 8 could be used for common loop sounders address 113 to 126 which allows 14 devices Note The cabling can be the same whatever method is used The devices DO NOT have to be number...

Страница 15: ...nel will now ask for the loop number and the loop address of device name to be entered Press enter to confirm loop 1 and enter again to confirm address 001 Enter the device label using the built in ke...

Страница 16: ...g the missing device could have a wrong address setting If many devices are missing check that they have power There may be more than one break in the cable the panel read all devices when it has a si...

Страница 17: ...off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off off off off on off off 16 on...

Страница 18: ...s DISABLE button and the ZONE 1 DISABLED LED will flash The panel is now in SELECT DISABLEMENT MODE 3 Press DISABLEMENT SELECT until the required zone or sounder circuit is lit Press DISABLEMENT CONFI...

Страница 19: ...another Zone or turn the control key switch to off position to exit test mode NOTE If testing a call point it will trigger the panel into alarm immediately but it will need to stay active for around...

Страница 20: ...of its add on components eg power supply If the device is missing NONE then Check the device has not been removed Check that there is power to the base Check that its address hasn t been changed compa...

Страница 21: ...t condition to reset If not consult your supplier Note that the system fault LED will Light if the Write enable switch is left on after entering a device message This is to warn of the risk of erasing...

Страница 22: ...ither side of the loop will power up Continue making more splits until the short has been found If The LEDs for a loop are flashing both on side a only both on side b only etc then this indicated a br...

Страница 23: ...Unit ZIOU 2 2 10 16 16 Zeta Sounder Control Module ZSCC 2 2 10 16 16 Zone Monitor Unit ZT ZM 2 2 50 126 126 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c Fyreye Address...

Страница 24: ...Detector 0 0001 Amp 100 A Typical Example A system comprises of 80 Addressable Optical detectors 80 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calcul...

Страница 25: ...oop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 11 CLA...

Страница 26: ...32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV...