![Zeta NPAD Скачать руководство пользователя страница 16](http://html2.mh-extra.com/html/zeta/npad/npad_installation-manual_3522121016.webp)
PREMIER AD INSTALLATION MANUAL.
Software:31/3/04 & LC6
Approved Document No: GLT.MAN-105
PAGE 16
Issue : 1.02 Authorised: GH Date: 15/03/2004
8.1
LOOP CONTENTS FAULT FINDING
If the loop contents are different to what was expected, then there may be some wrong
connections to devices (they are polarity sensitive), or double addresses on the loop. (A
double address is when 2 or more devices have been set to the same address, so they
both answer at the same time.)
If a panel detects a
double address, it will light the LEDs of the devices
with the problem. (NOTE: only detectors will light their
LED. Call points, sounders & interface modules will
not be indicated)
Return to the configuration menu & select option 5
(Dev status). Wait for the panel to read loop 1 address 001. (If loop 2 is needed, press
2,enter,001,enter).
The panel will give the device type & its analogue value. If the device is configured, there
will be an asterix (*) next to the device type. Number of devices should read 1 (a reading of
2 or more will mean a double address is present).
Press next to move to the next address on the loop. (The Previous button cannot be used
in this menu. It can only be used to scroll between multiple faults or alarms.) Read all
devices on the loop and compare with what was expected. If one address has 2 devices,
and another is “missing”, the missing device could have a wrong address setting. If many
devices are missing, check that they have power. There may be more than one break in
the cable (the panel read all devices when it has a single break, and will report a loop fault
after a minute or so).
8.2 ADDRESS - ZONE TABLE
On the Premier AD, each available address corresponds to a zone, with 1-16 being in
zone 1, 17-32 being in zone 2, 33-48 in zone3 etc.
The table below shows the dip switch settings for each address, and the zone that address
will be in.
Eg to set address 37, find 37 in the table. It is at sw 7,6,5 = 010, and sw 4,3,2,1= 0101
Remembering that 0 = ON & 1 = OFF, the switch settings for 37 are:
7=ON, 6=OFF, 5=ON, 4=ON, 3=OFF, 2=ON, 1=OFF
As an alternative to using this chart, use the table on the following page:-
SW
4,3,2,1
OOOO OOO1 OO1O OO11 O1OO O1O1 O11O O111 1OOO 1OO1 1O1O 1O11 11OO 11O1 111O 1111 LOOP 1
LOOP 2
SW OOO
N/A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15 ZONE 1
ZONE 9
7,6,5 OO1 16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31 ZONE 2 ZONE 10
O1O
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47 ZONE 3 ZONE 11
O11
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63 ZONE 4 ZONE 12
1OO
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79 ZONE 5 ZONE 13
1O1
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95 ZONE 6 ZONE 14
11O
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111 ZONE 7 ZONE 15
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
N/A ZONE 8 ZONE 16
Device Type: HEAT *
Value:26 No Devs:1
====================
Loop:1 Address:001
Содержание NPAD
Страница 1: ...INSTALLATION MANUAL...