Zeta NPAD Скачать руководство пользователя страница 16

PREMIER AD INSTALLATION MANUAL.  

 

 

Software:31/3/04 & LC6 

 

 

 

Approved Document No: GLT.MAN-105

 

 

 

 

PAGE 16

 

Issue : 1.02         Authorised: GH      Date: 15/03/2004

 

 

8.1

 

LOOP CONTENTS FAULT FINDING 

 
If the loop contents are different to what was expected, then there may be some wrong 
connections to devices (they are polarity sensitive), or double addresses on the loop. (A 
double address is when 2 or more devices have been set to the same address, so they 
both answer at the same time.) 

If a panel detects a 

double address, it will light the LEDs of the devices  
with the problem. (NOTE: only detectors will light their  
LED. Call points, sounders & interface modules will  
not be indicated)

 

 

Return to the configuration menu & select option 5  
(Dev status). Wait for the panel to read loop 1 address 001. (If loop 2 is needed, press 
2,enter,001,enter).  

 

The panel will give the device type & its analogue value. If the device is configured, there 
will be an asterix (*) next to the device type. Number of devices should read 1 (a reading of 
2 or more will mean a double address is present).  

 

Press next to move to the next address on the loop. (The Previous button cannot be used 
in this menu. It can only be used to scroll between multiple faults or alarms.) Read all 
devices on the loop and compare with what was expected. If one address has 2 devices, 
and another is “missing”, the missing device could have a wrong address setting. If many 
devices are missing, check that they have power. There may be more than one break in 
the cable (the panel read all devices when it has a single break, and will report a loop fault 
after a minute or so). 
 

8.2 ADDRESS - ZONE TABLE 

 

 
On the Premier AD, each available address corresponds to a zone, with 1-16 being in 
zone 1, 17-32 being in zone 2, 33-48 in zone3 etc. 

 

The table below shows the dip switch settings for each address, and the zone that address 
will be in.  

 

Eg to set address 37, find 37 in the table. It is at sw 7,6,5 = 010, and sw 4,3,2,1= 0101 

 

Remembering that 0 = ON & 1 = OFF, the switch settings for 37 are: 

 

7=ON, 6=OFF, 5=ON, 4=ON, 3=OFF, 2=ON, 1=OFF 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

As an alternative to using this chart, use the table on the following page:- 
 

  SW 

4,3,2,1 

                  

   

 

 

  

OOOO OOO1 OO1O OO11 O1OO O1O1 O11O O111 1OOO 1OO1 1O1O 1O11 11OO 11O1 111O  1111    LOOP 1  

LOOP 2

SW   OOO 

N/A 

10 

11 

12 

13 

14 

15    ZONE 1  

ZONE 9

7,6,5 OO1  16 

17 

18 

19 

20 

21 

22 

23 

24 

25 

26 

27 

28 

29 

30 

31    ZONE 2   ZONE 10

 O1O 

32 

33 

34 

35 

36 

37 

38 

39 

40 

41 

42 

43 

44 

45 

46 

47    ZONE 3   ZONE 11

 O11 

48 

49 

50 

51 

52 

53 

54 

55 

56 

57 

58 

59 

60 

61 

62 

63    ZONE 4   ZONE 12

 1OO 

64 

65 

66 

67 

68 

69 

70 

71 

72 

73 

74 

75 

76 

77 

78 

79    ZONE 5   ZONE 13

 1O1 

80 

81 

82 

83 

84 

85 

86 

87 

88 

89 

90 

91 

92 

93 

94 

95    ZONE 6   ZONE 14

 11O 

96 

97 

98 

99 

100 

101 

102 

103 

104 

105 

106 

107 

108 

109 

110 

111    ZONE 7   ZONE 15

 111 

112 

113 

114 

115 

116 

117 

118 

119 

120 

121 

122 

123 

124 

125 

126 

N/A   ZONE 8   ZONE 16

Device Type: HEAT * 

Value:26  No Devs:1 
====================

Loop:1   Address:001

Содержание NPAD

Страница 1: ...INSTALLATION MANUAL...

Страница 2: ...CABLE ENTRY 5 2 FIXING THE BACKBOX TO THE WALL 6 CONNECTING MAINS BATTERY POWER 12 6 1 CONNECTING MAINS POWER 6 2 CONNECTING THE BATTERIES 7 FIELD DEVICE TERMINATION 13 7 1 TERMINATING THE DETECTION A...

Страница 3: ...nal 1 1 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device If you are not familiar with binary check the table on page 17 o...

Страница 4: ...Reflective Beam Detector 100m 47 110 FE 50 AD Fyreye Plus Addressable Aspiration Detector 42 001 ZMT 8 Zeta Conventional Maxitone Sounder 42 002 ZMD 8 Zeta Conventional Miditone Sounder 42 004 ZST 8...

Страница 5: ...t person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer con...

Страница 6: ...e screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this...

Страница 7: ...are permitted on the loop There is no limit loop load permitting to the number of sounder bases that can be connected to a loop On the Premier AD Panel all Sounder Bases are always configured as commo...

Страница 8: ...C LOOP IN LOOP OUT LOOP IN LOOP OUT RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals a...

Страница 9: ...5W LOOP IN LOOP OUT LOOP IN LOOP OUT Zeta Sounder Controller Circuit ZSCC 48 110 24 Volt Supply LOOP IN LOOP OUT LOOP IN LOOP OUT 47K End of Line Resistor Zeta Input Output Unit ZIOU 48 105 47K EOL 0...

Страница 10: ...local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Fault Output FAULT This Output is energised in the quiescent condition In a fault condition...

Страница 11: ...f a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via on...

Страница 12: ...ference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOL...

Страница 13: ...Y Brass Glands Figure 6 Detector and Sounder Circuit Connection 7 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on th...

Страница 14: ...the example above zone 8 could be used for common loop sounders address 113 to 126 which allows 14 devices Note The cabling can be the same whatever method is used The devices DO NOT have to be number...

Страница 15: ...nel will now ask for the loop number and the loop address of device name to be entered Press enter to confirm loop 1 and enter again to confirm address 001 Enter the device label using the built in ke...

Страница 16: ...g the missing device could have a wrong address setting If many devices are missing check that they have power There may be more than one break in the cable the panel read all devices when it has a si...

Страница 17: ...off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off off off off on off off 16 on...

Страница 18: ...s DISABLE button and the ZONE 1 DISABLED LED will flash The panel is now in SELECT DISABLEMENT MODE 3 Press DISABLEMENT SELECT until the required zone or sounder circuit is lit Press DISABLEMENT CONFI...

Страница 19: ...another Zone or turn the control key switch to off position to exit test mode NOTE If testing a call point it will trigger the panel into alarm immediately but it will need to stay active for around...

Страница 20: ...of its add on components eg power supply If the device is missing NONE then Check the device has not been removed Check that there is power to the base Check that its address hasn t been changed compa...

Страница 21: ...t condition to reset If not consult your supplier Note that the system fault LED will Light if the Write enable switch is left on after entering a device message This is to warn of the risk of erasing...

Страница 22: ...ither side of the loop will power up Continue making more splits until the short has been found If The LEDs for a loop are flashing both on side a only both on side b only etc then this indicated a br...

Страница 23: ...Unit ZIOU 2 2 10 16 16 Zeta Sounder Control Module ZSCC 2 2 10 16 16 Zone Monitor Unit ZT ZM 2 2 50 126 126 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c Fyreye Address...

Страница 24: ...Detector 0 0001 Amp 100 A Typical Example A system comprises of 80 Addressable Optical detectors 80 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calcul...

Страница 25: ...oop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 11 CLA...

Страница 26: ...32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV...

Отзывы: