Zeta NPAD Скачать руководство пользователя страница 3

PREMIER AD INSTALLATION MANUAL.  

 

 

Software:31/3/04 & LC6 

 

 

 

Approved Document No: GLT.MAN-105

 

 

 

 

PAGE 3

 

Issue : 1.02         Authorised: GH      Date: 15/03/2004

 

 

1.PREMIER AD OVERVIEW 

 

The Premier AD is a 2-loop analogue addressable fire alarm control panel designed to EN54 part 2 & 
4. It has 2 addressable loops, each capable of having 126 devices, and also 4 independently 
operating sounder circuits. 
 
It has been designed to give the advantages of an addressable system, with the simplicity of a 
conventional system. To help achieve this, the Premier AD uses its LEDs as the Primary source of 
information, so in most cases, there is no reason to look at the screen, or access any menus. The 
screen is simply there to identify loop device fault locations, and to help in setting up the panel. 
 
 
 
 
 
 
 
 
 
 
The Premier AD has 4 sounder circuits, which are always configured as common sounders. They will 
activate with an alarm from any zone. 

 

The loop outputs (loop powered sounders, & sounder circuit controllers) can be set up as zonal, or 
common.  

 

If the sounder  is in a zone that contains a detector or input module, then that sounder will be zonal, 
and will only activate with an alarm in that zone.  

 

If the sounder  is in a zone that only contains output devices, then it will be common, and will activate 
with any alarm. 

 

The exception to this rule is a priority Call Point, which will start all sounders, even if they are set up 
as zonal. 

 
1.1 SETTING THE DEVICE ADDRESS (DETECTORS, CALL POINTS & 
SOUNDERS) 

 

The device address is set with a dip switch on the rear of the device. 

 

If you are not familiar with binary, check the 
table on page 17, or use the following rule: 

 

Switch 7 off = add 64,  
Switch 6 off = add 32,  
Switch 5 off = add 16,  
Switch 4 off = add 8,  
Switch 3 off = add 4,  
Switch 2 off = add 2,  
Switch 1 off = add 1. 

 

The example shown would be: 
switches 6, 4 & 1  
=32 + 8 + 1 = Address 41 

LIMITATIONS OF PRESET ZONE ALLOCATION 

 

The main disadvantage of this method of zone allocation is the maximum zone capacity of 16 devices. 
If a zone has more than 16 devices it will need to be split into smaller zones. 

 

Similarly, a zone with only one device would leave 15 empty addresses on that zone.  

 

This will not cause a problem if it is considered at the system design stage. 

1

7

6

5

4

3

2

8

ON

 

 
The address setting is binary, with 
the 

ON

 position being binary 

0

 , and 

the 

OFF

 position being binary 

1. 

Switch 8 is not used for setting the 
address, but sometimes has a 
devise specific function. (check 
instructions that

 

came with the 

device) 

Address 1-16 

 

Zone 1 (Zone 9 on loop 2) 

Address 17-32   

Zone 2 (Zone 10 on loop 2) 

Address 33-48   

Zone 3 (Zone 11 on loop 2) 

Address 49-64   

Zone 4 (Zone 12 on loop 2) 

Address 65-80   

Zone 5 (Zone 13 on loop 2) 

Address 81-96   

Zone 6 (Zone 14 on loop 2) 

Address 97-112  

Zone 7 (Zone 15 on loop 2) 

Address 113-126

Zone 8 (Zone 16 on loop 2) 

To simplify commissioning further, 
there is no zone allocation 
programming. Instead each loop is 
split into 8 zones, and each device is 
assigned to a zone by the address set 
with its 8 way dip switch. 

 

Содержание NPAD

Страница 1: ...INSTALLATION MANUAL...

Страница 2: ...CABLE ENTRY 5 2 FIXING THE BACKBOX TO THE WALL 6 CONNECTING MAINS BATTERY POWER 12 6 1 CONNECTING MAINS POWER 6 2 CONNECTING THE BATTERIES 7 FIELD DEVICE TERMINATION 13 7 1 TERMINATING THE DETECTION A...

Страница 3: ...nal 1 1 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device If you are not familiar with binary check the table on page 17 o...

Страница 4: ...Reflective Beam Detector 100m 47 110 FE 50 AD Fyreye Plus Addressable Aspiration Detector 42 001 ZMT 8 Zeta Conventional Maxitone Sounder 42 002 ZMD 8 Zeta Conventional Miditone Sounder 42 004 ZST 8...

Страница 5: ...t person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer con...

Страница 6: ...e screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this...

Страница 7: ...are permitted on the loop There is no limit loop load permitting to the number of sounder bases that can be connected to a loop On the Premier AD Panel all Sounder Bases are always configured as commo...

Страница 8: ...C LOOP IN LOOP OUT LOOP IN LOOP OUT RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals a...

Страница 9: ...5W LOOP IN LOOP OUT LOOP IN LOOP OUT Zeta Sounder Controller Circuit ZSCC 48 110 24 Volt Supply LOOP IN LOOP OUT LOOP IN LOOP OUT 47K End of Line Resistor Zeta Input Output Unit ZIOU 48 105 47K EOL 0...

Страница 10: ...local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Fault Output FAULT This Output is energised in the quiescent condition In a fault condition...

Страница 11: ...f a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via on...

Страница 12: ...ference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOL...

Страница 13: ...Y Brass Glands Figure 6 Detector and Sounder Circuit Connection 7 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on th...

Страница 14: ...the example above zone 8 could be used for common loop sounders address 113 to 126 which allows 14 devices Note The cabling can be the same whatever method is used The devices DO NOT have to be number...

Страница 15: ...nel will now ask for the loop number and the loop address of device name to be entered Press enter to confirm loop 1 and enter again to confirm address 001 Enter the device label using the built in ke...

Страница 16: ...g the missing device could have a wrong address setting If many devices are missing check that they have power There may be more than one break in the cable the panel read all devices when it has a si...

Страница 17: ...off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off off off off on off off 16 on...

Страница 18: ...s DISABLE button and the ZONE 1 DISABLED LED will flash The panel is now in SELECT DISABLEMENT MODE 3 Press DISABLEMENT SELECT until the required zone or sounder circuit is lit Press DISABLEMENT CONFI...

Страница 19: ...another Zone or turn the control key switch to off position to exit test mode NOTE If testing a call point it will trigger the panel into alarm immediately but it will need to stay active for around...

Страница 20: ...of its add on components eg power supply If the device is missing NONE then Check the device has not been removed Check that there is power to the base Check that its address hasn t been changed compa...

Страница 21: ...t condition to reset If not consult your supplier Note that the system fault LED will Light if the Write enable switch is left on after entering a device message This is to warn of the risk of erasing...

Страница 22: ...ither side of the loop will power up Continue making more splits until the short has been found If The LEDs for a loop are flashing both on side a only both on side b only etc then this indicated a br...

Страница 23: ...Unit ZIOU 2 2 10 16 16 Zeta Sounder Control Module ZSCC 2 2 10 16 16 Zone Monitor Unit ZT ZM 2 2 50 126 126 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c Fyreye Address...

Страница 24: ...Detector 0 0001 Amp 100 A Typical Example A system comprises of 80 Addressable Optical detectors 80 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calcul...

Страница 25: ...oop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 11 CLA...

Страница 26: ...32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV...

Отзывы: