Zeta NPAD Скачать руководство пользователя страница 21

PREMIER AD INSTALLATION MANUAL.  

 

 

Software:31/3/04 & LC6 

 

 

 

Approved Document No: GLT.MAN-105

 

 

 

 

PAGE 21

 

Issue : 1.02         Authorised: GH      Date: 15/03/2004

 

 

11.4 EARTH FAULTS 

 
An EARTH fault indicates that something is shorting to earth 
(usually through the cable screen). Disconnect the earth  
screens one at a time to determine the problem line. 

 

(Note: connecting other equipment , eg an oscilloscope , to  
the panel can give an earth fault) 

 

The voltage between battery –Ve and earth should be 14-16 volts. If it is not, the voltage should 
indicate what is shorting to earth. 

 

***DO NOT DISCONNECT THE MAINS EARTH CONNECTION. THIS WILL CAUSE A PROBLEM 
WITH THE PANELS OPERATION***

 

 

11.5 DOUBLE ADDRESS 
 

This indicates that a double address has been detected. This usually happens if a head is replaced 
during maintenance, and its address has been wrongly set. The panel will report 2 fault addresses, 
one will be the double address, and the other will be a missing device. As a further aid to finding the 
fault, the panel will light the LEDs of any detectors with a double address (Call points, Sounders & I/O 
units will not be indicated as they have no panel controlled LED to light up) 
 

11.6 SYSTEM FAULT 

 

A system fault is an abnormal microprocessor running condition due to various unexpected 
phenomena  

 

This will result in the panel attempting to correct itself.  Should this fault occur, the System Fault LED, 
General Fault LED, General Fault relay and fault internal buzzer will be constantly active until the 
control keyswitch is turned from off position to control enable position.  This should cause this fault 
condition to reset. If not, consult your supplier. 
**Note that the system fault LED will Light if the Write enable switch is left on after entering a device 
message. This is to warn of the risk of erasing the stored data. Use the keyswitch to reset after the 
switch has been turned off. 

 
11.7 PRE-ALARM 
 
This is not a fault condition. The panel has detected a high reading from one of the devices on 
the loop. This could be caused by a fire starting (in which case it acts as an early warning), or 
it could be caused by a contaminated head. The panel will report the location of the problem 
device, which should then be investigated. 
 
11.8 SOUNDER FAULTS 

 
On the premier AD there are separate fault indications for each  
sounder circuit, and a separate one for the loop sounders. 
 
Conventional sounders: 
 
The fault LED will flash for an open circuit fault, and will be steady for a short circuit fault. 
 
Check that the correct END of Line resistor has been fitted. (10K – brown, black, orange, gold) 
Check that all sounder fuses are OK (FS4, FS5,FS6 & FS7 – 250mA TD) 
If working on an existing installation, check that the devices are 

polarised

. (See Page 5) 

Check cable continuity (remove from panel and measure continuity. Should read 10K) 

 

Loop controlled sounders: 

 

If sounder circuit controllers are used, check as per conventional sounder, and also check its power 
supply. 
For loop powered sounders, check that all sounders are communicating, and check their analogue 
value. If a sounder is returning a value less than 8, then it has detected an internal fault and should 
be replaced. 
If they are not communicating, then check that they have power, and that the power is connected the 
correct way. If they have power, they may be damaged. Try a replacement if available. 
 

  ***  FAULT  *** 

 

    Earth Fault

 

  ***  FAULT  *** 

 

    Sounder Fault

 

Содержание NPAD

Страница 1: ...INSTALLATION MANUAL...

Страница 2: ...CABLE ENTRY 5 2 FIXING THE BACKBOX TO THE WALL 6 CONNECTING MAINS BATTERY POWER 12 6 1 CONNECTING MAINS POWER 6 2 CONNECTING THE BATTERIES 7 FIELD DEVICE TERMINATION 13 7 1 TERMINATING THE DETECTION A...

Страница 3: ...nal 1 1 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device If you are not familiar with binary check the table on page 17 o...

Страница 4: ...Reflective Beam Detector 100m 47 110 FE 50 AD Fyreye Plus Addressable Aspiration Detector 42 001 ZMT 8 Zeta Conventional Maxitone Sounder 42 002 ZMD 8 Zeta Conventional Miditone Sounder 42 004 ZST 8...

Страница 5: ...t person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer con...

Страница 6: ...e screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this...

Страница 7: ...are permitted on the loop There is no limit loop load permitting to the number of sounder bases that can be connected to a loop On the Premier AD Panel all Sounder Bases are always configured as commo...

Страница 8: ...C LOOP IN LOOP OUT LOOP IN LOOP OUT RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals a...

Страница 9: ...5W LOOP IN LOOP OUT LOOP IN LOOP OUT Zeta Sounder Controller Circuit ZSCC 48 110 24 Volt Supply LOOP IN LOOP OUT LOOP IN LOOP OUT 47K End of Line Resistor Zeta Input Output Unit ZIOU 48 105 47K EOL 0...

Страница 10: ...local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Fault Output FAULT This Output is energised in the quiescent condition In a fault condition...

Страница 11: ...f a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via on...

Страница 12: ...ference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOL...

Страница 13: ...Y Brass Glands Figure 6 Detector and Sounder Circuit Connection 7 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on th...

Страница 14: ...the example above zone 8 could be used for common loop sounders address 113 to 126 which allows 14 devices Note The cabling can be the same whatever method is used The devices DO NOT have to be number...

Страница 15: ...nel will now ask for the loop number and the loop address of device name to be entered Press enter to confirm loop 1 and enter again to confirm address 001 Enter the device label using the built in ke...

Страница 16: ...g the missing device could have a wrong address setting If many devices are missing check that they have power There may be more than one break in the cable the panel read all devices when it has a si...

Страница 17: ...off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off off off off on off off 16 on...

Страница 18: ...s DISABLE button and the ZONE 1 DISABLED LED will flash The panel is now in SELECT DISABLEMENT MODE 3 Press DISABLEMENT SELECT until the required zone or sounder circuit is lit Press DISABLEMENT CONFI...

Страница 19: ...another Zone or turn the control key switch to off position to exit test mode NOTE If testing a call point it will trigger the panel into alarm immediately but it will need to stay active for around...

Страница 20: ...of its add on components eg power supply If the device is missing NONE then Check the device has not been removed Check that there is power to the base Check that its address hasn t been changed compa...

Страница 21: ...t condition to reset If not consult your supplier Note that the system fault LED will Light if the Write enable switch is left on after entering a device message This is to warn of the risk of erasing...

Страница 22: ...ither side of the loop will power up Continue making more splits until the short has been found If The LEDs for a loop are flashing both on side a only both on side b only etc then this indicated a br...

Страница 23: ...Unit ZIOU 2 2 10 16 16 Zeta Sounder Control Module ZSCC 2 2 10 16 16 Zone Monitor Unit ZT ZM 2 2 50 126 126 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c Fyreye Address...

Страница 24: ...Detector 0 0001 Amp 100 A Typical Example A system comprises of 80 Addressable Optical detectors 80 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calcul...

Страница 25: ...oop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 11 CLA...

Страница 26: ...32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV...

Отзывы: