14. PANEL SPECIFICATIONS
14.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION VALUE
ENCLOSURE SIZE
480 x 395 x 100 mm
TOP CABLE ENTRIES
20 x 19mm DIA GROMMETED ENTRIES
BOTTOM CABLE ENTRIES
10 x 19mm KNOCKOUT ENTRIES
REAR CABLE ENTRIES
2 SNAP OUTS, 60 x 20mm
14.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
230V AC +/- 10% @ 50/60 Hz
BATTERY VOLTAGE
24V DC (2 X 12V SLA BATTERY)
SYSTEM VOLTAGE
24V DC NOMINAL (18 – 32 V)
SYSTEM VOLTAGE RIPPLE
2V PK-PK MAX
CHARGER SIZE
UP TO 7AH in 24 Hours
ZONE VOLTAGE
24V DC NOMINAL (+9 volt data)
SOUNDER ALARM OUTPUTS
4 x 250mA @ 24V DC (Nominal)
AUXILIARY FAULT OUTPUT
1 x RELAY SELV (1A MAX)
AUXILIARY FIRE OUTPUT
1 x RELAY SELV (1A MAX)
NUMBER OF LOOPS
2 LOOPS
MAXIMOM NUMBER OF ZONES
16 ZONES
MAXIMUM LOOP CAPACITY
126 DEVICES PER LOOP
MAXIMUM ZONE CAPACITY
16 DEVICES PER ZONE
MAXIMUM LOOP RESISTANCE
25 ohms
MAXIMUM LOOP CAPACITANCE
0.3µF
MAXIMUM VOLTAGE PICKUP ALLOWED
50mV
REMOTE SOUNDER ACTIVATION
VIA N/O CONTACTS
SOUNDER END OF LINE DEVICE
10 K RESISTOR
CHARGER VOLTAGE
28.3V @ 22-24
o
C (NO BATTERY CONNECTED)
LOOP SHORT CIRCUIT PROTECTION
750mA
CHARGER SHORT CIRCUIT PROTECTION
Batteries less than 20V
TOTAL CHARGER OUTPUT
1.5 Amp