PREMIER AD INSTALLATION MANUAL.  

 

 

Software:31/3/04 & LC6 

 

 

 

Approved Document No: GLT.MAN-105

 

 

 

 

PAGE 14

 

Issue : 1.02         Authorised: GH      Date: 15/03/2004

 

 

 
8. DESIGNING THE SYSTEM & CONFIGURING THE FACP 
 

Configuring the premier AD is a fairly straightforward matter. It just takes a bit of thought to 
zone allocation during the system design stage. 

 

1. Decide on the zone allocation for the system. Each zone can have a maximum of 16 
devices fitted. Consider the simplified 3-storey building below. 
 

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

ZONE 1: DEVICE ADDRESS 1 TO 16
ZONE 2: DEVICE ADDRESS 17 TO 32
ZONE 3: DEVICE ADDRESS 33 TO 48

ZONE 7: DEVICE ADDRESS 97 TO 112

ZONE 4: DEVICE ADDRESS 49 TO 64
ZONE 5: DEVICE ADDRESS 65 TO 80
ZONE 6: DEVICE ADDRESS 81 TO 96

 

 

 

2. If loop controlled sounders are to be used, decide if they should operate zonally, or 
common. If zonal operation is required, then they should have addresses within the zone 
that contains the detectors that  will activate them. If the loop sounders are to be common, 
then they should be addressed within a zone that contains only output devices. (In the 
example above, zone 8 could be used for common loop sounders: address 113 to 126, 
which allows 14 devices) 

 

Note

: The cabling can be the same whatever method is used. The devices DO NOT have 

to be numbered sequentially on the loop. It can be changed from one method to the other, 
provided there are free addresses to change the sounder’s zones.

  

 
 
 
 

3 After the system has been installed, and the cabling  
checked and the addresses of each device set, connect  
the loops to the fire alarm panel and power up the system  
(mains & batteries). It should say “system normal, and only  
the green Power LED will be lit. There will be the letter  
“B” in the bottom left hand corner. This stands for Benign, 
or controls OFF. 

 

 
4. Turn the keyswitch to the Controls Enabled Position.  
The Letter “B” will now change to an “A”, for controls 
Active.  
 

 

5. Enter the access code 3 6 9. This will take you to the 
configuration menu. In this Menu there are options to  
view loop contents, configure the panel, edit the device  
message, or view the status of each device. The Covered  
option will exit from the menu, and return the panel to 
normal operation. 

  Fire Alarm Panel 
To EN54  pt2 & pt4 

   System Normal 

                   B

  Fire Alarm Panel 

To EN54  pt2 & pt4 
   System Normal 

                   A

Configuration Menu 
1:Lp1 Dev 4:Messages

2:Lp2 Dev 5:Dev Stat
3:Config  6:Covered 

Содержание NPAD

Страница 1: ...INSTALLATION MANUAL...

Страница 2: ...CABLE ENTRY 5 2 FIXING THE BACKBOX TO THE WALL 6 CONNECTING MAINS BATTERY POWER 12 6 1 CONNECTING MAINS POWER 6 2 CONNECTING THE BATTERIES 7 FIELD DEVICE TERMINATION 13 7 1 TERMINATING THE DETECTION A...

Страница 3: ...nal 1 1 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device If you are not familiar with binary check the table on page 17 o...

Страница 4: ...Reflective Beam Detector 100m 47 110 FE 50 AD Fyreye Plus Addressable Aspiration Detector 42 001 ZMT 8 Zeta Conventional Maxitone Sounder 42 002 ZMD 8 Zeta Conventional Miditone Sounder 42 004 ZST 8...

Страница 5: ...t person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer con...

Страница 6: ...e screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this...

Страница 7: ...are permitted on the loop There is no limit loop load permitting to the number of sounder bases that can be connected to a loop On the Premier AD Panel all Sounder Bases are always configured as commo...

Страница 8: ...C LOOP IN LOOP OUT LOOP IN LOOP OUT RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals a...

Страница 9: ...5W LOOP IN LOOP OUT LOOP IN LOOP OUT Zeta Sounder Controller Circuit ZSCC 48 110 24 Volt Supply LOOP IN LOOP OUT LOOP IN LOOP OUT 47K End of Line Resistor Zeta Input Output Unit ZIOU 48 105 47K EOL 0...

Страница 10: ...local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Fault Output FAULT This Output is energised in the quiescent condition In a fault condition...

Страница 11: ...f a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via on...

Страница 12: ...ference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOL...

Страница 13: ...Y Brass Glands Figure 6 Detector and Sounder Circuit Connection 7 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on th...

Страница 14: ...the example above zone 8 could be used for common loop sounders address 113 to 126 which allows 14 devices Note The cabling can be the same whatever method is used The devices DO NOT have to be number...

Страница 15: ...nel will now ask for the loop number and the loop address of device name to be entered Press enter to confirm loop 1 and enter again to confirm address 001 Enter the device label using the built in ke...

Страница 16: ...g the missing device could have a wrong address setting If many devices are missing check that they have power There may be more than one break in the cable the panel read all devices when it has a si...

Страница 17: ...off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off off off off on off off 16 on...

Страница 18: ...s DISABLE button and the ZONE 1 DISABLED LED will flash The panel is now in SELECT DISABLEMENT MODE 3 Press DISABLEMENT SELECT until the required zone or sounder circuit is lit Press DISABLEMENT CONFI...

Страница 19: ...another Zone or turn the control key switch to off position to exit test mode NOTE If testing a call point it will trigger the panel into alarm immediately but it will need to stay active for around...

Страница 20: ...of its add on components eg power supply If the device is missing NONE then Check the device has not been removed Check that there is power to the base Check that its address hasn t been changed compa...

Страница 21: ...t condition to reset If not consult your supplier Note that the system fault LED will Light if the Write enable switch is left on after entering a device message This is to warn of the risk of erasing...

Страница 22: ...ither side of the loop will power up Continue making more splits until the short has been found If The LEDs for a loop are flashing both on side a only both on side b only etc then this indicated a br...

Страница 23: ...Unit ZIOU 2 2 10 16 16 Zeta Sounder Control Module ZSCC 2 2 10 16 16 Zone Monitor Unit ZT ZM 2 2 50 126 126 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c Fyreye Address...

Страница 24: ...Detector 0 0001 Amp 100 A Typical Example A system comprises of 80 Addressable Optical detectors 80 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calcul...

Страница 25: ...oop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 11 CLA...

Страница 26: ...32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV...

Отзывы: