PREMIER AD INSTALLATION MANUAL.  

 

 

Software:31/3/04 & LC6 

 

 

 

Approved Document No: GLT.MAN-105

 

 

 

 

PAGE 19

 

Issue : 1.02         Authorised: GH      Date: 15/03/2004

 

 

10. TEST MODE 

 
10.1 WHY USE TEST MODE

 

 

To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is 
available. 
 
When a detector or manual call point is triggered on any zone in Test, the Alarm sounders operate for 
approximately eight seconds on and four seconds off.  This cycle continues until the cause of the 
Alarm is removed (either by the test smoke clearing from the detector or the manual call point being 
reset), sounders will then stop activating. 
 
Should an Alarm occur on a zone that is not programmed to test, the Fire Alarm Panel will cancel the 
test mode. After the cause of the alarm has been checked, and the panel reset, test mode will have 
to be selected again to resume testing. 
 

10.2 TO PROGRAMME ZONE IN TEST MODE 

 
NOTE:  Only 

one zone

 can be programmed in test at any one time. 

 
1.  Insert and turn control key to enabled position; 

 

2.  Press TEST Button, followed by the code 

2 4 8.

 

 

3.  The GENERAL TEST LED will light steady, and Zone 1 test led will flash. 

 

4.  Press TEST FUNCTION SELECT button to select the zone to be tested.  

 

5.  Press confirm to enter test mode for this function. The LED will now be steady. 

 

6.  Once testing of that zone is completed, press TEST FUNCTION SELECT button to move to 

another Zone or turn the control key switch to off position to exit test mode. 

 

NOTE: If testing a call point, it will trigger the panel into alarm immediately, but it will need to 
stay active for around 8 seconds before the panel registers it as a test mode alarm. If the call 
point is active for less than 8 seconds, the sounders WILL NOT RESET. 
 
8.3 TO PROGRAM SOUNDER CIRCUITS IN TEST MODE 

 
NOTE:  Only 

one sounder circuit or the loop sounders

 can be programmed in test mode at any 

one time.  

NOTE:  Only the ADDRESSABLE SOUNDERS can be tested with the loop sounder one man 
test mode. The ASSOCIATED SOUNDER BASES cannot be tested this way because of their 
slow stop/start time.

 

 

1.  Insert and turn control key to enabled position; 

 

2.  Press TEST Button, followed by the code 2 4 8. 

 

3.  Zone 1 test led will flash. 

 

4.  Press TEST FUNCTION SELECT button to select the sounder to be tested.  

 

5.  Press confirm to enter test mode for this function. The LED will now be steady. 

 

6.  The Sounders will now pulse 3 seconds on, 3 seconds off until they are taken out of test 

mode. This allows all the sounders to be tested for correct operation, and dB output. 

 

7.  Once testing of that sounder circuit is completed, press TEST FUNCTION SELECT button to 

move to another circuit, or turn the control key switch to off position to exit test mode 

 
 

 

To test associated sounder bases, use the stop/start sounder button (evacuate). Note that the 
sounders will take up to 9 seconds to start. 
 
***NOTE*** 
Associated sounder bases are controlled by the detector. 

Removing the detector will leave the 

sounder base inoperative. 

Содержание NPAD

Страница 1: ...INSTALLATION MANUAL...

Страница 2: ...CABLE ENTRY 5 2 FIXING THE BACKBOX TO THE WALL 6 CONNECTING MAINS BATTERY POWER 12 6 1 CONNECTING MAINS POWER 6 2 CONNECTING THE BATTERIES 7 FIELD DEVICE TERMINATION 13 7 1 TERMINATING THE DETECTION A...

Страница 3: ...nal 1 1 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device If you are not familiar with binary check the table on page 17 o...

Страница 4: ...Reflective Beam Detector 100m 47 110 FE 50 AD Fyreye Plus Addressable Aspiration Detector 42 001 ZMT 8 Zeta Conventional Maxitone Sounder 42 002 ZMD 8 Zeta Conventional Miditone Sounder 42 004 ZST 8...

Страница 5: ...t person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer con...

Страница 6: ...e screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this...

Страница 7: ...are permitted on the loop There is no limit loop load permitting to the number of sounder bases that can be connected to a loop On the Premier AD Panel all Sounder Bases are always configured as commo...

Страница 8: ...C LOOP IN LOOP OUT LOOP IN LOOP OUT RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals a...

Страница 9: ...5W LOOP IN LOOP OUT LOOP IN LOOP OUT Zeta Sounder Controller Circuit ZSCC 48 110 24 Volt Supply LOOP IN LOOP OUT LOOP IN LOOP OUT 47K End of Line Resistor Zeta Input Output Unit ZIOU 48 105 47K EOL 0...

Страница 10: ...local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Fault Output FAULT This Output is energised in the quiescent condition In a fault condition...

Страница 11: ...f a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via on...

Страница 12: ...ference Once the mains is connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOL...

Страница 13: ...Y Brass Glands Figure 6 Detector and Sounder Circuit Connection 7 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on th...

Страница 14: ...the example above zone 8 could be used for common loop sounders address 113 to 126 which allows 14 devices Note The cabling can be the same whatever method is used The devices DO NOT have to be number...

Страница 15: ...nel will now ask for the loop number and the loop address of device name to be entered Press enter to confirm loop 1 and enter again to confirm address 001 Enter the device label using the built in ke...

Страница 16: ...g the missing device could have a wrong address setting If many devices are missing check that they have power There may be more than one break in the cable the panel read all devices when it has a si...

Страница 17: ...off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off off off off on off off 16 on...

Страница 18: ...s DISABLE button and the ZONE 1 DISABLED LED will flash The panel is now in SELECT DISABLEMENT MODE 3 Press DISABLEMENT SELECT until the required zone or sounder circuit is lit Press DISABLEMENT CONFI...

Страница 19: ...another Zone or turn the control key switch to off position to exit test mode NOTE If testing a call point it will trigger the panel into alarm immediately but it will need to stay active for around...

Страница 20: ...of its add on components eg power supply If the device is missing NONE then Check the device has not been removed Check that there is power to the base Check that its address hasn t been changed compa...

Страница 21: ...t condition to reset If not consult your supplier Note that the system fault LED will Light if the Write enable switch is left on after entering a device message This is to warn of the risk of erasing...

Страница 22: ...ither side of the loop will power up Continue making more splits until the short has been found If The LEDs for a loop are flashing both on side a only both on side b only etc then this indicated a br...

Страница 23: ...Unit ZIOU 2 2 10 16 16 Zeta Sounder Control Module ZSCC 2 2 10 16 16 Zone Monitor Unit ZT ZM 2 2 50 126 126 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c Fyreye Address...

Страница 24: ...Detector 0 0001 Amp 100 A Typical Example A system comprises of 80 Addressable Optical detectors 80 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calcul...

Страница 25: ...oop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault 11 CLA...

Страница 26: ...32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV...

Отзывы: