SIMPLICITY PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-107
PAGE 4
Issue 3.16 Author: NRPJ Date: 21/09/2017
2. PRODUCT DESIGN INFORMATION
2.1 FIRE ALARM CONTROL SECTION
The Simplicity Plus Fire Alarm Control and Indicating Equipment (CIE) Has been designed to EN54-2:1998 A1 + A2 - Fire
Detection & Fire Alarm Systems – Control & Indicating Equipment.
As well as meeting the requirements of EN54-2:1998 A1 + A2, the Simplicity Plus also has the following options with
requirements:-
Clause 7.8
Output to fire alarm devices (Option with requirements)
Clause 7.12
Dependencies on more than one alarm signal (Option with requirements)
Clause 8.3
Fault signals from points (Option with requirements)
Clause 9.5
Disablement of addressable points (Option with requirements)
Clause 10
Test Condition (Option with requirements)
The Simplicity Plus also has the following ancillary functions not required by the Standard:-
Class Change Input to allow remote activation of sounders.
Serial repeater output (RS485).
Serial Output Port (RS232).
2.2 POWER SUPPLY SECTION
The Simplicity Plus Fire Alarm Panels Power Supply Equipment (PSE) Has been designed to EN54-4:1998 A1 + A2 - Fire
Detection & Fire Alarm Systems – Power Supply Equipment.
The PSE has been designed to charge batteries up to 12 Ah within the time limits specified by EN54-4.
The PSE will draw a maximum of 25mA from the battery in the event of mains failure.
The PSE is a switching power supply, with a supply rating (IMAX) of 2.0 Amps.
The PSE has a 750mA limited charger output.
2.3 ENVIRONMENTAL
It will operate in ambient temperatures of –5 to 40
o
C.
It will operate in a relative humidity of up to 95% (non condensing).
It will withstand vibrations between 5 & 150 Hz.
The CIE & PSE should be maintained as described in section 3 of the User Manual, Maintenance Guide & Log Book.