SIMPLICITY PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-107
PAGE 10
Issue 3.16 Author: NRPJ Date: 21/09/2017
6.2 FIRST FIX
6.2.1 MOUNTING THE FIRE ALARM PANEL
The Simplicity comes with many cable entry holes. If another entry hole is required, it is strongly recommended that the
panels door be removed to avoid accidental damage. Also, the termination and Power Supply PCBs should be removed
and stored in a safe place. This would also help while fixing the back box to the wall.
6.2.2 FIXING THE BACK BOX TO THE WALL
Figure 2: Plan view inside the enclosure without PCBs. Side view for surface installation.
Fix the enclosure to the wall using the three mounting holes provided.
Check the build & condition of the wall to decide a suitable screw fixing.
The mounting holes are designed for No 8 roundhead or countersunk woodscrews (or similar).
Remove any debris from the enclosure.
Take care not to damage the FACP during installation.
6.2.3 PLANNING CABLE ENTRY
Fig.2 above shows the location of the cable entries to facilitate planning of wiring (home runs) to be brought to the panel.
The grommets can be easily removed by a push from inside the control panel box.
If a grommet is removed, fill the hole with a brass cable gland. If any knockout is removed, but subsequently not used, it
should be covered up.
The 230Va.c. Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back
box. (Refer to “Connecting the Mains” on Following Page).