SIMPLICITY PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-107
PAGE 27
Issue 3.16 Author: NRPJ Date: 21/09/2017
Simplicity system, we refer to this as the Zonal to Common sounder time.
Select option 3 (Sounder) from the alarm operation menu. This zonal to common sounder time
can either be disabled, i.e. alarms stay zonal, or it can be enabled, i.e. all the sounders will start
after the programmed time delay.
Sounder Operation
Zonal-Common Time
Disabled
ENTER to Confirm
To alter this delay, go to the System Menu and select option 4 (Timing)
System Menu
1: Clock 4: Timing
2: Zones 5: Misc
3: Alarms 6: Reset
The panel will bring up the following menu. Select option 1 (Zonal to common)
Alarm Timing
1: Zonal to Common
2: Alarm Verify
The panel will now show the currently selected delay time. This can be set between 30 seconds
and 10 minutes, in 15 second increments, using the previous and next buttons. Press enter to
confirm the selected time.
Zonal-Common Time
0:30
ENTER to Confirm
12.8.4 ASSOCIATED SOUNDER BASE SETTINGS
On previous Simplicity Panels, associated sounder bases have always been common acting.
There is now an option for them to be zonal. In the Alarm Operation Menu, select option 4
(bases).
Alarm Operation
1: Det 4: Bases
2: MCP 5: I/O
3: Sounder
Press Prev / Next to select common or Zonal operation, then press enter.
Sounder Operation
Sounder Bases
Common
ENTER to Confirm
12.9 CHANGING THE ALARM RESPONSE – I/O UNITS
Because a system could have several I/O units, each reacting to different types of events the simplicity system adopts the
following method for configuring I/O units:-
1. Select a default I/O unit operation (This is done from the Alarm Operation Menu)
This will then be the default operation of all I/O units on the system.
2. Any I/O units which need a different operation can be edited individually from the edit device screen
12.9.1 TYPES OF I/O UNIT OPERATION
The simplicity now has the following types of I/O operation:-
Common
Operates output on ANY alarm
Zonal Detector
Operates its output on a DETECTOR alarm from its own ZONE
Zonal All
Operates its output on any alarm from its own ZONE
Own Input
Operates its output ONLY when its own INPUT is triggered
Panel Link
Special type used for Inter-panel link. Output operates on any alarm , EXCEPT from its own
address, AND the input is non latching and behaves similar to class change.
Manual Alarm
Operates output on ANY MCP alarm
Detector Alarm
Operates output on ANY Detector alarm
Zonal MCP
Operates its output on a MCP alarm from its own ZONE
12.9.2 SETTING DEFAULT I/O UNIT OPERATION
To set the simplicity panels default I/O operation, enter configuration menu 2, then select config
system to bring up the system menu.
System Menu
1: Clock 4: Timing
2: Zones 5: Misc
3: Alarms 6: Reset