SIMPLICITY PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-107
PAGE 30
Issue 3.16 Author: NRPJ Date: 21/09/2017
12.12 PROTOCOL
The Simplicity Panel now supports 2 addressable protocols. The Original Zeta Addressable Protocol, and the new Fyreye
Mk II Protocol. The New protocol has been introduced to allow future development of our products, but is unfortunately
incompatible with the original Protocol.
Check the information below and select the correct protocol for the devices you have on the system.
Changing the protocol
From Configuration menu 2, Select configure system (option
6)
Then from the Misc Settings menu, select option 3 (Protocol)
Press Prev / Next to
select Standard or
Fyreye-Mk2 protocol,
and then press ENTER
NOTE: The Factory Default option will reset the panel to the
Fyreye Mk II Protocol. If your system is running the standard
Zeta protocol devices, then you will need to change the
protocol (as described above) before the panel will see the
devices
Original Fyreye Detectors (1 LED)
FEAO2000 FEAH2000
Use STANDARD Protocol setting
Fyreye Extra Detectors (2 LED)
FEAOE2000 FEAHE2000
Use
STANDARD
Protocol setting
Fyreye MK II Detectors (8 LED)
FEII-AOP FEII-AHR
Use
FYREYE MK II
Protocol setting
Select Protocol
Fyreye-Mk2
ENTER to Confirm