SIMPLICITY PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-107
PAGE 43
Issue 3.16 Author: NRPJ Date: 21/09/2017
20. STANDBY BATTERY REQUIREMENTS
The Following Table shows the Quiescent, Fault & alarm currents of the main parts of a Simplicity Fire Alarm System
.
DEVICE
PRODUCT CODE
I
Q
(MA)
I
FLT
(MA)
I
ALM
(MA)
MAX
PER
LOOP
MAX
PER
SYSTEM
SIMPLICITY PLUS 64 Fire Alarm Panel
SP-64
90
105
115
N/A
1
SIMPLICITY PLUS 126 Fire Alarm Panel
SP-126
90
105
115
N/A
1
SIMPLICITY PLUS 252 Fire Alarm Panel
SP-252
115
120
130
N/A
1
Premier Addressable REPEATER PANEL
REP-AD
200
220
220
N/A
4*
Fyreye MKII Addressable Optical Smoke Detector
MKII-AOP
0.5
N/A
5.0
126
252
Fyreye MKII Addressable Heat Detector
MKII-AHR
0.5
N/A
5.0
126
252
Fyreye MKII Fixed Temperature Heat Detector
MKII-AHF
0.5
N/A
5.0
126
252
Fyreye MKII Addressable Opto-Heat Detector
MKII-AOH
0.5
N/A
5.0
126
252
Zeta Addressable Call Point (EN54)
ZT-CP3/AD
0.45
N/a
2.3
126
252
Zeta Weatherproof Addressable Call Point
ZT-CP3/AD/WP
0.45
N/a
2.3
126
252
Zeta Addressable Input Module with SCI
ZAI-MI
1.0
1.25
3.6
32
64
Zeta Addressable Input/ Output Module with SCI
ZAIO-MI
1.0
1.25
2.0
16
32
Zeta Addressable Input/ Output Module with SCI –
mains switching
ZAIO-MI /230
0.9
2.8
19
10
20
Zeta Sounder Control Module
ZASC-MI
0.6
0.6
0.8
16
32
Zone Monitor Unit
ZAZM-MI
3.5
12.6
13.2
10
20
Fyreye Addressable Beam Detector (5-50m)
ZT-BEAM + SMM/B
5
7
9
16
32
Sandwich Sounder Base
MKII-SSB
0.6
N/a
7.5
32
64
Zeta Addressable Maxitone Sounder
MKII/AMT
0.6
N/a
7.0
32
64
Zeta Addressable Maxitone Sounder flasher
MKII/AMTF
0.6
N/a
10.6
24
48
Zeta Addressable Xtratone Sounder
MKII/AXT
0.6
N/a
7.5
32
64
Zeta Addressable Maxitone Sounder flasher
MKII/AXTF
0.6
N/a
7.5
24
48
Zeta Addressable Remote LED Indicator
MKII-ARL/W(C)
0.45
N/a
2.1
32
64
Zeta Conventional wire Remote LED
MKII-RL/W(C)
0
N/a
10
32
64
Conventional Sounders (via a sounder Control Circuit)
Zeta Conventional Maxitone Sounder
ZMT/8
0
N/a
15
N/a
N/a
Zeta Conventional Miditone Sounder
ZMD/8
0
N/a
15
N/a
N/a
Zeta Conventional Securetone Sounder
ZST/8
0
N/a
15
N/a
N/a
Zeta Conventional Megatone Sounder
ZIDC
0
N/a
200
N/a
N/a
Zeta Conventional Flasher
ZFL2RR
0
N/a
90
N/a
N/a
Zeta Conventional Sounder Flasher
ZLT/8RR
0
N/a
110
N/a
N/a
Zeta Conventional 6” Bells
ZTB6B/24
0
N/a
25
N/a
N/a
Zeta Conventional 8” Bells
ZTB8B
0
N/a
35
N/a
N/a
Conventional Detectors (via a Zone Monitor)
Fyreye MKII Conventional Optical Detector
MKII-OP
0.06
N/a
25
N/a
N/a
Fyreye MKII Conventional Heat Detector (A2R)
MKII-HR
0.04
N/a
25
N/a
N/a
Fyreye MKII Conventional Heat Detector (A2S)
MKII-HF
0.04
N/a
25
N/a
N/a
Fyreye MKII Conventional Opto-Heat Detector
MKII-Oh
0.06
N/a
25
N/a
N/a
GSM COMMUNICATOR
GSM-COM
200
500
500
N/A
1
TCP-IP COMMUNICATOR
TCP-IP
80
80
80
N/A
1
* The Simplicity can only power 1 repeater. Any subsequent ones will need a separate power supply.