background image

SIMPLICITY PLUS INSTALLATION MANUAL

 

 

 

 

Approved Document No: GLT.MAN-107 

 

  

PAGE 28

 

Issue 3.16         Author: NRPJ      Date: 21/09/2017 

 

Select Option 3 (Alarms) to bring up the alarm operation Menu. 
 
Select option 5 (I/O). This brings up the following screen.  

Alarm Operation 
1: Det    4: Bases 
2: MCP    5: I/O 
3: Sounder 

 

Press Prev & Next to select the default operation, then press enter. 

I/O Unit Operation 

Common 

 

 ENTER to Confirm 

12.9.3 SETTING INDIVIDUAL I/O UNIT OUTPUT OPERATION 

To alter the operation mode of an individual I/O unit, go to configuration menu 2. 
 
Select Edit Device. 

Configuration Menu 2 
4:Configure Loops 
5:Edit Device 
6:Config System    < 

 

Scroll to the required Address. 
 
Press V to cycle through the different Variations of I/O configuration. 

I/O-COM    

         

 

 

Analog:  16  Normal 
Interface to Main FA 
Zone:01       Ad:013 

 

12.9.4 SETTING INDIVIDUAL I/O UNIT INPUT OPERATION 

 

 
To alter the INPUT mode of an individual I/O unit, go to configuration menu 2 
 
Select Edit Device. 
 
Scroll to the required Address 
 
Press Button “I” (for Input) to cycle through the different Triggering

 

Options of I/O configuration 

 
The different options are:- 
 
Letter 

Description  

Use 

A  

AUTOMATIC ALARM 

I/O signals Detector alarm when operated. Default setting. Used when 
device being monitored is Automatically triggered. 

M  

MANUAL CALL POINT ALARM 

I/O signals a MCP alarm when operated. Used when device being 
monitored is Manually triggered, and the system is set to distinguish 
manual & automatic alarms. 

P  

PREALARM 

I/O signals a Pre-Alarm when operated. Used when a device being 
monitored needs to give a warning signal , but not an alarm signal. 

F  

FAULT 

I/O signals a Fault Signal when operated. Used when a device being 
monitored does not have a normally closed fault relay 

D  

DISABLE RELAYS 

I/O sets all connected I/O relays as disabled when operated. Used when 
user testing of the panel needs to suspend relay operation to avoid 
shutting down connected equipment. Turning off the input re-enables the 
relays 

 

 
 
 

I/O Zn-D  

    P                           

Normal 
Plant Room 
Zone:01         ID:01 

Содержание Simplicity Plus 126

Страница 1: ...SIMPLICITY PLUS INSTALLATION MANUAL Approved Document No GLT MAN 107 Issue 3 16 Author NRPJ Date 21 09 2017 ONE OR TWO LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION MANUAL...

Страница 2: ...ontrol Module 15 7 1 6 ZAZM MI Conventional Zone Module 16 7 1 7 Xtratone Sounder Sounder Flasher 16 7 1 8 Sandwich Sounder 16 7 1 9 Remote LED Indicator 16 7 1 10 Isolator Base 17 7 2 MAXIMUM LOOP LE...

Страница 3: ...DISABLEMENTS DURING A FIRE ALARM CONDITION 36 17 DISABLEMENT 37 17 1 ZONE DISABLEMENT 37 17 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED 37 17 3 DEVICE DISABLEMENT 37 17 4 VIEWING DISABLEMENTS 38 17 4...

Страница 4: ...ic Always handle PCBs by their sides and avoid touching the legs of any components Keep the PCBs away from damp dirty areas e g in a small cardboard box 1 2 SAFETY PRECAUTIONS DURING NORMAL OPERATION...

Страница 5: ...irements The Simplicity Plus also has the following ancillary functions not required by the Standard Class Change Input to allow remote activation of sounders Serial repeater output RS485 Serial Outpu...

Страница 6: ...e individual devices or whole zones Detector LED sounder can be operated from the menu to help identify devices Panel software version can be viewed through menu The 64 could be upgraded to a 126 by c...

Страница 7: ...PANEL LOOP ADDRESS LOOP ADDRESS DEVICE LABEL 20 CHARACTERS for device PLUS 20 Characters for the ZONE 20 CHARACTERS PREALARM PRESET 45 PRESET 45 DETECTOR SENSITIVITY PRESET 55 PRESET 55 ZONE ALLOCATI...

Страница 8: ...in a step by step manner the procedure for the basic design and installation of the Simplicity Plus Range of Fire Alarm Control Panels It gives detailed instructions on how to use all the features on...

Страница 9: ...1 to 96 Zone 7 Addresses 97 to 112 Zone 1 Addresses 1 to 16 First Zone 4 Addresses 49 to 64 Zone 5 Addresses 65 to 80 Zone 1 Addresses 1 to 16 Ground Zone 2 Addresses 17 to 32 Zone 3 Addresses 33 to 4...

Страница 10: ...5839 Pt1 2013 Clause 26 are Standard fire resisting cable to PH30 classification of EN 50200 Enhanced fire resisting cable to PH120 classification of EN 50200 Note that all cables should be at least 1...

Страница 11: ...all using the three mounting holes provided Check the build condition of the wall to decide a suitable screw fixing The mounting holes are designed for No 8 roundhead or countersunk woodscrews or simi...

Страница 12: ...hould be passed twice through the provided ferrite This is made easier by removing the outer insulation The cable is then connected to the Live Earth and Neutral connections marked on the power supply...

Страница 13: ...of Battery 1 to the black battery charger lead Connect the ve of Battery 2 to the red battery charger lead The ve of the first battery is connected to the ve of the second battery using the FUSED lin...

Страница 14: ...olator fitted This is to prevent a short circuit fault in one zone affecting another zone Note that some Devices for example a sounder controller circuit may require a separate 24 volt supply to opera...

Страница 15: ...t terminal on the call point The following terminals are used for connecting the call point 2 x Negative in terminals note if you only connect to the negative in terminals then the isolator is bypasse...

Страница 16: ...d of line resistor value is 20K and the trigger resistor value is 1K 7 1 5 ZASC MI Sounder Control Module The ZASC requires a external 24vdc power supply as shown in the above diagram The EOL for the...

Страница 17: ...minals in the back box of the device Please refer to the above diagram 7 1 8 Sandwich Sounder The sandwich sounder has no wiring to connect as it just clips straight on to a standard base It will run...

Страница 18: ...using 1 5mm cable can have a maximum loop run of 1250m end to end 7 3 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS The device address is set with a dip switch on the rear of the device 1...

Страница 19: ...ON ON OFF ON ON 59 OFF OFF ON OFF OFF OFF ON 102 ON OFF OFF ON ON OFF OFF 17 OFF ON ON ON OFF ON ON 60 ON ON OFF OFF OFF OFF ON 103 OFF OFF OFF ON ON OFF OFF 18 ON OFF ON ON OFF ON ON 61 OFF ON OFF OF...

Страница 20: ...it might be possible to speed up the sounder base start stop time See CONFIGURING ASSOCIATED SOUNDERS section 8 3 SANDWICH SOUNDER BASES ADDRESSD MODE The sandwich sounder can be given an address wit...

Страница 21: ...take a few seconds There are 2 methods to speed up the stop times of these sounders 1 For ease of functional checking during installation the simplicity panel assumes that every detector found during...

Страница 22: ...condition It can be connected to emergency lights local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc Extra alarm relays can be achieved by fit...

Страница 23: ...NATING THE WIRING Figure 6 Cable connections All cables entering the enclosure should have cable glands which will prevent unwanted openings in the enclosure The Addressable Loop circuits should be co...

Страница 24: ...upports up to 4 repeaters Connections See Section 21 for the serial repeater connections 11 2 SERIAL PRINTER CONNECTION The Simplicity has an RS232 Serial output that transmits panel events as they oc...

Страница 25: ...nu 2 In this menu there are options to Configure the loops to edit each device and to configure the system options The arrow in the bottom left hand corner shows that pressing PREVIOUS button will ret...

Страница 26: ...every detector has a sounder base or if most of the detectors have a sounder base this speed up operation will have little or no effect 1 Press enter NEXT followed by 369 to enter Configuration Menu...

Страница 27: ...area The minimum number of addresses per zone is 2 Zone Boundaries Zone 1 001 010 ENTER to Change All 8 zones do not need to be use i e the 126 device version could be configured as 6 zones of 21 dev...

Страница 28: ...common or Zonal operation then press enter Sounder Operation Sounder Bases Common ENTER to Confirm 12 9 CHANGING THE ALARM RESPONSE I O UNITS Because a system could have several I O units each reactin...

Страница 29: ...o to configuration menu 2 Select Edit Device Scroll to the required Address Press Button I for Input to cycle through the different Triggering Options of I O configuration The different options are Le...

Страница 30: ...nguage Bank 2 English Hungarian Serbian Lithuanian Configuration Menu 2 4 Configure Loops 5 Edit Device 6 Config System 12 11 SOFTWARE VERSIONS From Configuration menu 2 Select configure system option...

Страница 31: ...l From Configuration menu 2 Select configure system option 6 Then from the Misc Settings menu select option 3 Protocol Press Prev Next to select Standard or Fyreye Mk2 protocol and then press ENTER NO...

Страница 32: ...ector stays in alarm by the end of the verification delay the system will go into full alarm If another detector WITHOUT verification setting or a call point goes into alarm the panel will go straight...

Страница 33: ...se back to all common resets system timers 4 Devices Clears device information from memory and clears device label device configuration 6 All Performs 2 3 4 in one operation When you select to reset a...

Страница 34: ...not to ring any sounders 2 MCP Choose MCP to cause zonal alarm or common alarm for sounders 3 SOUNDER Select if the sounders have a zonal to common time out when triggered zonally 4 Bases Select if a...

Страница 35: ...e following messages Optical Changed Analog 25 Fault Fl 3 Bedroom 303 Zone 01 Ad 016 FAULT MEANING Changed The device had been changed with one of a different type since last configuration The message...

Страница 36: ...nd the Zone loop and address if appropriate Next Previous buttons will cycle through the list Event 173 25 01 2007 17 21 Device Alarm Zone 01 Lp 1 Ad 013 System The Simplicity also records other non c...

Страница 37: ...s in the second zone that went into alarm etc To view the alarms chronologically the event log must be used FIRE First Z01 2 of 2 Last Z02 Kitchen Zone 02 Ad 017 16 2 VIEWING FAULTS DURING A FIRE ALAR...

Страница 38: ...and the Zone or Sounder LED will come on steady along with the GENERAL DISABLEMENT LED This section is now disabled NOTE Call points in this zone will also be disabled To keep the call points functio...

Страница 39: ...e screen will show Zone Disablement Zone 1 Zone Enabled Disabled Devices 0 If a zone is disabled the screen will show Zone Disablement Zone 1 Zone Disabled Disabled Devices 0 If there are one or more...

Страница 40: ...is zone can now be tested with smoke spray The Detector will light its LED until the smoke clears then it will reset The Sounders the fire relay are not operated during test mode Once testing of that...

Страница 41: ...doubt contact your supplier If the wiring polarity is correct check that there is no cable break on the loop If there is a break the panel will report the break after 60 seconds or so and inside the p...

Страница 42: ...nomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and fault internal buzzer will be constantly active...

Страница 43: ...vices wait for the zone fault LED check the addresses in that zone then there is probably a short circuit on the loop look for isolators lit Yellow or flashing The missing devices should give an indic...

Страница 44: ...13 2 10 20 Fyreye Addressable Beam Detector 5 50m ZT BEAM SMM B 5 7 9 16 32 Sandwich Sounder Base MKII SSB 0 6 N a 7 5 32 64 Zeta Addressable Maxitone Sounder MKII AMT 0 6 N a 7 0 32 64 Zeta Addressab...

Страница 45: ...Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr TSBY 24 Hr IQP 0 105A Quiescent current for panel IQD 80 x...

Страница 46: ...LOOP 1 Connect to detector wiring loop 1 4 FIRE RELAY Volt free relay Operates on any alarm 5 FAULT RELAY Volt free relay normally energised Operates on any fault 6 CLASS CHANGE Remote input to opera...

Страница 47: ...for the second 24 V output 6 B FUSE Fuse for the second 24V output 7 BATTERY Battery connection 2 x 12V SLA batteries wired in series 8 FACTORY ADJUST Charger adjust pot DO NOT ADJUST 9 THERM Battery...

Страница 48: ...SOUNDER ALARM OUTPUTS LOOP POWERED SOUNDERS ONLY AUXILIARY FAULT OUTPUT 1 x FAULT RELAY SELV 1A NORM ENERG AUXILIARY FIRE OUTPUT 1 x FIRE RELAY SELV 1A NUMBER OF LOOPS SIMPLICITY PLUS 64 1 LOOP SIMPL...

Страница 49: ...2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings Simplicity Plus SP 64 M SP 126 M SP 252 M Provided options Output to fire al...

Страница 50: ...d enclosure designed for 7AH comment in battery calc section refers to Original Plastic version of panel 3 13 29 8 2012 Corrected Max loops Devs to reflect 2 loop version sect 22 2 NOTE Use PDF Printe...

Отзывы: