PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
7
2.4 PANEL SPECIFICATIONS - ELECTRICAL
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
230 V AC + 10% / - 15%
BATTERY VOLTAGE
2 x 12V SLA (27.6V DC @ 20 C) (7Ah – 17Ah)
POWER SUPPLY
NON-INTEGRAL (SWITCH MODE)
DC OUTPUT: Vmax = 31V ,Vmin = 19V
I max A: 4.1 A
Ripple & Noise: <= 0.6V
CIE DC INPUT VOLTAGE
Vmax = 31.5V, Vmin = 19V
CHARGER VOLTAGE
27.6V
CONVENTIONAL SOUNDER OUTPUT (x2)
I max: 450mA
Quiescent voltage: 5 to 9V DC
Active voltage: 18 to 28V DC
End-of-Line Resistance: 4k7 ohm 0.25W
FIRE RELAY OUTPUT (x1)
(C,NO,NC)
Contact rating: 30V DC @ 1A
FAULT RELAY OUTPUT (x1)
Normally Energized (C,NO,NC)
Contact rating: 30V DC @ 1A
LOOP VOLTAGE
Vmax 32 V DC Vmin 26 V DC
MAXIMUM LOOP CURRENT
500 mA
NUMBER OF LOOPS
4
MAXIMUM NUMBER OF ZONES
250 Zones
MAXIMUM LOOP CAPACITY
250 Addresses
MAXIMUM LOOP LENGTH
2 km
MAXIMUM LOOP RESISTANCE
44 ohm (22 ohms + to +, 22 ohms – to -)
MAXIMUM LOOP CAPACITANCE
500nF
MAXIMUM LOOP BAUD RATE
1024 Bits Per Second
MAXIMUM NETWORK SIZE
32 nodes
MAXIMUM DISTANCE BETWEEN NODES
1 km
CABLE TYPE
Fire Proof 2 core + screen 1.5 mm
2
ALPHA NUMERIC (LCD) DISPLAY
40 x 4 characters
LED INDICATIONS
Fire (Zones 1 – 20)
Fault / Disable / Test (Zones 1 – 20)
KEY ENTRY
12 alphanumeric
6 navigational
3 mandatory
4 menu functions (F1, F2, F3, F4)
ENVIRONMENTAL DATA
Temperature: -5 to 40 C
Relative Humidity: 95% Non-Condensing
will withstand vibrations between 5 & 150 Hz
ENCLOSURE RATING
IP 30
OTHER PORTS
USB
RS485 via plug in network card
RS232 via plug in network card
TCP/IP via plug in network card
EN54-2 Optional Functions with Requirements
7.8, 7.11, 8.3, 9.5, 10
www.acornfiresecurity.com