PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
27
6.4 SETTING THE DEVICE ADDRESS (DETECTORS, CALL POINTS, SOUNDERS &
INTERFACE UNITS)
6.4.1 SOFT AND HARD PROGRAMMING
The MKII Handheld Programmer is designed to complement all MKII devices and to assist the commissioning engineer on site. The
unit will softly address all devices without using the incorporated dip-switch on the field devices.
Smoke and heat detectors can be tested when plugged on the programmer and alarm LED’s can be verified prior to installation.
The MKII Programmer can also re-program the OPT-HEAT detectors to either heat or smoke detector.
If the address programming tool is not available, the device Address can still be set with a DIP switch on the rear of the device.
1
7
6
5
4
3
2
8
ON
The Address setting is binary, with the ON position being binary
0, and the OFF position being binary 1.
If you are not familiar with binary, check the table on page 14, or use the
following rule:
Switch 8 off = Add 128
Switch 7 off = Add 64
Switch 6 off = Add 32
Switch 5 off = Add 16
Switch 4 off = Add 8
Switch 3 off = Add 4
Switch 2 off = Add 2
Switch 1 off = Add 1
The example shown would be: switches 6, 4 & 1 = 32 + 8 + 1 = Address 41
6.4.2 DIP SWITCH ADDRESS SETTINGS - FULL TABLE
ADDRESS
SWITCHES
ADDRESS
SWITCHES
ADDRESS
SWITCHES
1
2
3
4
5
6
7 8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
0
=
N
O
T
U
S
E
D
43
=
OFF OFF ON OFF ON OFF ON ON 86
=
ON OFF OFF ON OFF ON OFF ON
1
=
OFF ON ON ON ON ON ON ON 44
=
ON ON OFF OFF ON OFF ON ON 87
=
OFF OFF OFF ON OFF ON OFF ON
2
=
ON OFF ON ON ON ON ON ON
45
=
OFF ON OFF OFF ON OFF ON ON
88
=
ON ON ON OFF OFF ON OFF ON
3
=
OFF OFF ON ON ON ON ON ON
46
=
ON OFF OFF OFF ON OFF ON ON
89
=
OFF ON ON OFF OFF ON OFF ON
4
=
ON ON OFF ON ON ON ON ON
47
=
OFF OFF OFF OFF ON OFF ON ON
90
=
ON OFF ON OFF OFF ON OFF ON
5
=
OFF ON OFF ON ON ON ON ON
48
=
ON ON ON ON OFF OFF ON ON
91
=
OFF OFF ON OFF OFF ON OFF ON
6
=
ON OFF OFF ON ON ON ON ON
49
=
OFF ON ON ON OFF OFF ON ON
92
=
ON ON OFF OFF OFF ON OFF ON
7
=
OFF OFF OFF ON ON ON ON ON
50
=
ON OFF ON ON OFF OFF ON ON
93
=
OFF ON OFF OFF OFF ON OFF ON
8
=
ON ON ON OFF ON ON ON ON
51
=
OFF OFF ON ON OFF OFF ON ON
94
=
ON OFF OFF OFF OFF ON OFF ON
9
=
OFF ON ON OFF ON ON ON ON
52
=
ON ON OFF ON OFF OFF ON ON
95
=
OFF OFF OFF OFF OFF ON OFF ON
10
=
ON OFF ON OFF ON ON ON ON
53
=
OFF ON OFF ON OFF OFF ON ON
96
=
ON ON ON ON ON OFF OFF ON
11
=
OFF OFF ON OFF ON ON ON ON
54
=
ON OFF OFF ON OFF OFF ON ON
97
=
OFF ON ON ON ON OFF OFF ON
12
=
ON ON OFF OFF ON ON ON ON
55
=
OFF OFF OFF ON OFF OFF ON ON
98
=
ON OFF ON ON ON OFF OFF ON
13
=
OFF ON OFF OFF ON ON ON ON
56
=
ON ON ON OFF OFF OFF ON ON
99
=
OFF OFF ON ON ON OFF OFF ON
14
=
ON OFF OFF OFF ON ON ON ON
57
=
OFF ON ON OFF OFF OFF ON ON
100
=
ON ON OFF ON ON OFF OFF ON
www.acornfiresecurity.com