PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
30
6.6 FAULT RELAY (VOLTAGE FREE CHANGEOVER CONTACTS)
The fault relay (R. FAULT) is energised in the quiescent condition. When any type of fault occurs, this is indicated by the fault relay
to ensure fail safe operation, even in the event of total power loss. That is, the normally open contact will be closed when there is
no fault, and open when there is a fault. This should be taken into account when any device is connected to the fault relay.
6.7 AUXILIARY DC OUTPUT
This 24V DC output is provided to support low power requirements (450mA max). A separate power supply will be required for
higher current applications.
6.8. FIELD DEVICE TERMINATION
S+ S- ER+ R- E
Connect loop
Earth Screens to
Earth Bar
Figure 7: Connecting cables to the Quatro panel
All cables should enter the enclosure via the cable gland, and the cable shields must be connected to the earth bar. Figure 7
illustrates how the mains cable and an addressable loop cable are connected to the panel. All other screens must be terminated at
the brass earth strip.
MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH GROMMETS.
7- PANEL SET UP
7.1 INITIAL PANEL SET UP
The Premier Quarto panel is normally configured ready for installation. But if the panel has been altered (Extra loop cards added for
example), then various settings may need to be altered.