PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
11
3.3 NAVIGATING THE PANEL MENUS
The Quatro panel has 2 menus, user and installer. Entering the user code (Default 1111) accesses the user menu and entering the
Installer password (Default 2222) accesses the Installer menu.
The Left hand side of the screen shows the list of options. The up & down arrows on the cursor pad are used to move between
options. The Currently selected option is shown with an asterisk. If an option has a right facing arrow, it means that option has a
sub menu that will be displayed on the right hand side of the screen if selected.
The center dividing line may have an arrow at the top or bottom of the screen. This means that you can move the
asterisk
cursor in
the indicated direction.
On the sub menu, there is also the asterisk and top/bottom arrow’s to show the highlighted option and the scroll directions.
To enter a sub-menu, press the right cursor.
To select an item press the accept (Tick) button
To leave the sub menu press the left cursor
3.3.1 Navigating a set-up screen.
The Premier Quatro has several configuration screens. They all work in generally the same way
The Highlighted field is shown as <xxxxxxx>
A non-highlighted field is shown as [xxxxx]
Left & right cursors are used to move between fields
Up and down cursors are used to cycle values in the fields.
Numeric fields can have the value entered directly (with leading zeros if necessary)
Text fields Use up & down cursors to move the cursor in the string.
3.4 CONTROLS
The panel contains the following mandatory controls. They can only be operated when the key on the front of the panel has been
turned clockwise from OFF to CONTROLS ENABLED. The CONTROLS ACTIVE LED indicates that the controls have been enabled.
START / STOP SOUNDERS
This control can be used by authorised personnel to stop or silence the sounders whilst the panel is in the fire alarm condition. This
control will alternately stop and start the sounders (i.e. silence and sound the alarms).
SILENCE BUZZER
This control silences the panel’s internal buzzer which is always activated when a fire or a fault has been detected.
RESET
After a fire or false alarm has been fully investigated and dealt with, operating this control resets the fire alarm condition. The same
control is used to reset from a fault condition.
It is good practice to stop the sounders before resetting the panel. However, pressing the RESET control whilst the sounders are still
active will silence the sounders as well as resetting the fire alarm condition (although it is recommended that you always silence
the sounders via the ‘stop sounders’ button before resetting the panel).
OTHER CONTROLS
In addition to the 3 mandatory controls, the keypad also provides:
12 alphanumeric (including ENTER and CANCEL), 6 navigational (
▲
,
▼
,
◄
,
►
,
,
) and 4 menu functions (F1, F2, F3, F4) keys.
Each menu function key corresponds to the function or command label in square brackets which is displayed on the bottom line of
the LCD immediately above the function key.