Страница 3: ...t can be monitored and periodically sent to the KNX bus to inform other devices The most outstanding features of KLIC PA are Bidirectional control of Panasonic A C units through the connection wires R...

Страница 4: ...device into the programming mode making the associated LED 1 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode The LED will blink...

Страница 5: ...of KLIC PA as well as on security and installation procedures please refer to the device Datasheet bundled in the device packaging and also available at http www zennio com 1 3 START UP AND POWER LOSS...

Страница 6: ...ATION Figure 3 General The General screen is shown in the first place containing the following parameters Heartbeat Periodic Alive Notification disabled enabled 1 this parameter lets the integrator in...

Страница 7: ...Off and AC On Off Status allow switching on value 1 and off value 0 the A C unit or reading the current status respectively AC Temperature Setpoint and AC Temperature Setpoint Status allow setting the...

Страница 8: ...ll not work properly with KLIC PA ETS PARAMETERISATION When Inputs has been activated in the General parameters screen the following drop down lists will be available for the selection of the specific...

Страница 9: ...ZN1IO DETEC P motion detector is compatible with a variety of Zennio devices However depending on the device it is actually being connected to the functionality may differ slightly Therefore please re...

Страница 10: ...ution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after execu...

Страница 11: ...f flaps or vanes positioning direct positioning swing movement and standby function depending on the A C unit Moreover KLIC PA allows configuring several advanced functions Setpoint limits to restrict...

Страница 12: ...the state of the A C unit which therefore notifies KLIC PA periodically about the current state When KLIC PA is notified about a change it updates the status objects and sends them to the KNX bus In a...

Страница 13: ...KLIC PA http www zennio com Technical Support http support zennio com 13 Figure 6 A C Gateway Configuration OPERATION MODES Figure 7 A C Gateway Configuration Operation modes...

Страница 14: ...ling and Heating mode Simplified Mode disabled enabled in addition to the AC Mode and AC Mode Status 1 Byte objects available by default it is possible to commute and to verify the current operation m...

Страница 15: ...ps or vanes that direct the air flow outwards To that end KLIC PA provides a percentage control Flaps disabled enabled allows the percentage control type which will be applied in flaps Flaps position...

Страница 16: ...e respectively Swing Object Polarity 0 Swing On 1 Swing Off 0 Swing Off 1 Swing On sets the polarity of the above objects Besides KLIC PA allows activating the Standby function in case of being availa...

Страница 17: ...following table show the percentage values that correspond to the three levels Control Values Status Value Level Sent to the Unit 1 33 33 1 minimum 34 66 66 2 67 100 100 3 maximum Table 4 Fan speed Th...

Страница 18: ...oint from below in the Cooling Dry and Auto modes and from above in the Heating and Auto modes provided that the limits are still within the predefined limits of the A C unit When KLIC PA receives an...

Страница 19: ...C Unit use as reference to do the temperature control In addition is possible to configure the next option External Reference Temperature Object disabled enabled enables a 2 Byte object AC External Re...

Страница 20: ...perating time The operating time of the A A machine in hours and or seconds can be known The available parameters in ETS are Seconds disabled enabled enables the 2 Byte object AC Operating time s This...

Страница 21: ...event trigger Automatic off will be also active if the unit is previously in off state so the unit will not be able of being on until this situation finishes During the temporary switch off state KLI...

Страница 22: ...each of them in a set of orders to be sent to the A C unit upon the reception of scene trigger values through the KNX bus See section 2 4 3 2 4 2 INITIAL CONFIGURATION The custom initial configuratio...

Страница 23: ...ng 1 2 3 4 5 This option only will be visible in case of having enabled Flaps on the contrary this section will appear as Not Available Speed Last Before Restart Automatic 1 2 3 4 5 Setpoint disabled...

Страница 24: ...s ETS PARAMETRISATION After enabling this function see section 2 4 1 a new tab named Scenes will be incorporated to the tab tree It allows setting up different scenes up to 5 consisting each of them i...

Страница 25: ...enabled Value No Change Only available if Setpoint parameter remains disabled 10 25 32 Note this setpoint value may be modified by the setpoint limits during runtime 2 4 4 ERROR HANDLING KLIC PA is ca...

Страница 26: ...PA and the status will be the previous to the error activation Errors in the A C unit errors reported by the A C unit itself KLIC PA can notify the KNX bus about the reported error code although refer...

Страница 27: ...Probe Error 0 No Alarm 1 Alarm 14 20 26 1 Bit I C W DPT_Enable 0 1 Ix Input Lock 0 Unlock 1 Lock 15 21 27 1 Bit C T DPT_Switch 0 1 Ix Short Press 0 Sending of 0 1 Bit C T DPT_Switch 0 1 Ix Short Pres...

Страница 28: ...f 0 63 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Short Press Save Scene Sending of 128 191 1 Bit I O C T R W DPT_Switch 0 1 Ix Switch Sensor Edge Sending of 0 or 1 1 Byte C T DPT_Value_1_Ucount 0 25...

Страница 29: ...by 100 0x7 Dec by 1 0x8 Stop 0x9 Inc by 100 0xF Inc by 1 Ix Long Press Darker Long Pr Darker Release Stop 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0x9 Inc by 100 0x...

Страница 30: ...otection Ix Presence State HVAC Auto Comfort Standby Economy Building Protection 39 68 97 1 Bit O C T R DPT_Occupancy 0 1 Ix Presence State Binary Binary Value 1 Bit O C T R DPT_Ack 0 1 Ix Presence Sl...

Страница 31: ...2_Count 32768 32767 DPT_Value_Temp 273 00 670760 00 185 186 187 188 189 190 191 192 4 Bytes I C W DPT_Value_4_Count 2147483648 2147483647 LF 4 Byte Data Entry x 4 Byte Data Entry 193 194 195 196 197 1...

Страница 32: ...I C W DPT_Scaling 0 100 AC Speed Percentage Control 0 Automatic 0 4 33 3 S1 33 8 66 6 S2 67 1 100 S3 215 1 Byte O C T R DPT_Scaling 0 100 AC Speed Percentage Control Status Automatic 0 S1 33 3 S2 66 7...

Страница 33: ...c Off Delay 0 3600 s 0 Disabled 229 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 AC Reference Temperature Status Effective Control Temperature C 230 2 Bytes I C W DPT_Value_Temp 273 00 670760 00 AC...