ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the
specifications or restrictions from both the KNX standard or the application programme itself.
Note: objects related to channels 5 and 6 are only present in DALIBOX Broadcast 6CH.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
O
C T R - -
DPT_Alarm
0/1
Error: Power Supply
0 = Normal; 1 = Power Supply Failure
2
1 Bit
I
C - - W -
DPT_Enable
0/1
Manual Control Lock
0 = Unlock; 1 = Lock
1 Bit
I
C - - W -
DPT_Enable
0/1
Manual Control Lock
0 = Lock; 1 = Unlock
3, 27, 51,75, 99, 123
1 Bit
I
C - - W -
DPT_Switch
0/1
[Cx] On/Off
0 = Off; 1 = On
4, 28, 52, 76, 100, 124
4 Bit
I
C - - W -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
0x2 (Dec. by 50%)
0x3 (Dec. by 25%)
0x4 (Dec. by 12%)
0x5 (Dec. by 6%)
0x6 (Dec. by 3%)
0x7 (Dec. by 1%)
0x8 (Stop)
0x9 (Inc. by 100%)
0xA (Inc. by 50%)
0xB (Inc. by 25%)
0xC (Inc. by 12%)
0xD (Inc. by 6%)
0xE (Inc. by 3%)
0xF (Inc. by 1%)
[Cx] Relative Dimming
4 bits Dimmer Control
5, 29, 53, 77, 101, 125
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[Cx] Absolute Dimming
1 byte Dimmer Control
6, 30, 54, 78, 102, 126
1 Bit
O
C T R - -
DPT_Switch
0/1
[Cx] On/Off (Status)
0 = Off; 1 = On
7, 31, 55, 79, 103, 127
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Cx] Dimming Value (Status)
0 - 100%
8, 32, 56, 80, 104, 128
2 Bytes
I
C - - W -
DPT_TimePeriodSec
0 - 65535
[Cx] Dimming Time 1
Time in Seconds
9, 33, 57, 81, 105, 129
2 Bytes
I
C - - W -
DPT_TimePeriodSec
0 – 65535
[Cx] Dimming Time 2
Time in Seconds
10, 34, 58, 82, 106, 130
2 Bytes
I
C - - W -
DPT_TimePeriodSec
0 - 65535
[Cx] Dimming Time 3
Time in Seconds
11, 35, 59, 83, 107, 131
1 Bit
I
C - - W -
DPT_Switch
0/1
[Cx] Custom On/Off 1
0 = Off; 1 = On
12, 36, 60, 84, 108, 132
1 Bit
I
C - - W -
DPT_Switch
0/1
[Cx] Custom On/Off 2
0 = Off; 1 = On
13, 37, 61, 85, 109, 133
1 Bit
I
C - - W -
DPT_Start
0/1
[Cx] Simple Timer
0 = Deactivate; 1 = Activate
14, 38, 62, 86, 110, 134
1 Bit
I
C - - W -
DPT_Start
0/1
[Cx] Flashing
0 = Deactivate; 1 = Activate