Once the simple timer function has been enabled, the “
[Cx] Simple Timer
” one-bit
object becomes enabled too, making it possible to trigger a switch-on by sending it the
value “1” or a switch-off by sending it the value “0”. Both actions can be delayed
according to the following parameters:
On Delay
: sets a delay between the reception of the simple timer trigger
order (value “1” through object “
[Cx] Simple Timer
”) and the actual switch-on
of the channel, in the range 0 to 255 seconds or minutes.
Off Delay
: sets a delay between the reception of the simple timer stop order
(value “0” through object “
[Cx] Simple Timer
”) and the actual switch-off of
the channel, in the range 0 to 255 seconds or minutes.
On Duration
: sets the time the output channel must remain on before being
automatically switched off (unless the value “0” is received through “[Cx]
Simple Timer”, which will switch the channel off immediately), in the range 0
to 255 seconds or minutes. The value “0” (default option) will disable the
automatic switch-off, thus making the channel remain on.
Action in Case of Retriggering
: sets the action to be performed in case the
value “1” is received several times.
Nothing
: the current time count will not be restarted.
Restart
: the time count of the On Duration will be restarted from zero.
Multiply
: the time count of the On Duration will become ‘n’ times the
configured time, being ‘n’ the number of times the value “1” is received.
On Value
: sets a specific dimming percentage (0% to 100%) to be applied to
the channel during the “on” stage.
Dimming Time
: “At Once”, “Dimming Time 1”, “Dimming Time 2”, “Dimming
Time 3” (see “Dimming times” in section 2.2.1).
Note
:
the simple timer function will be interrupted whenever any other
dimming action is commanded, no matter if it falls within the On Duration or
during the On/Off delays.