ANNEX I. AUTOMATIC AIR RECIRCULATION IN
COOLING MODE
If this function
automatic air recirculation in cooling mode
is activated and the system
is operating in cooling mode:
When the valve is closed, the fan must remain on or switch on.
In case the input control command is lower than the minimum value to activate
the valve, the fan speed will be the value specified by parameter and modifiable
by object “
[FCn] Fan: Automatic Air Recirculation Speed
”.
Once recirculation is active, events such as fan coil deactivation, a mode change or a
bus failure can force the fan to stop.
Whereas, if
automatic air recirculation in cooling mode
is not enabled or the system
is operating in heating mode:
When receiving a control command lower than the value that activates the valve,
both the valve and the fan will take a value of 0%.
The Table 1 below shows the specific effects of having or not having the automatic air
recirculation function enabled in different situations. The table is generated starting with
the valve closed.