Fan Coil ‘Analog’

 

https://www.zennio.com                                                                   

Technical Support:

 

https://support.zennio.com 

 

1

 

INTRODUCTION 

A variety of Zennio devices incorporate the 

‘Analog’ Fan Coil control module

, which 

enables the control external fan coil units where both the opening of the valves and the 

fan speed can be controlled through 

analog voltage outputs

The fan coil units to be controlled may be 

two-pipe

 or 

four-pipe

. Each 

pair of pipes

 

constitute a water circuit controlled by a 

valve

, whose position is managed by a 0 

– 10 

VDC analogue signal. 

Typically, the two water circuits of a four-pipe fan coil unit correspond to the 

cooling

 and 

heating

  functions,  being  therefore  both  modes  available  during  the  device  operation. 

The single water circuit of a two-pipe fan coil unit, on the other and, may be configured 

for 

cooling, heating or both.

 

Important:  In  order  to  confirm  whether  a  particular  device  or  application  program 

incorporates the fan coil analog function, please refer to the device user manual, as 

there may be significant differences between the functionality of each Zennio device. 

Moreover, to access the proper fan coil analog user manual, it is always recommended 

to  make  use  of  the  specific  download  links  provided  at  the  Zennio  website 

(

www.zennio.com

) within the section of the specific device being parameterised. 

 

 

 

Содержание Analog

Страница 1: ...Fan coil Analog Control Module for Fan Coil Units with Analog Voltage Valves USER MANUAL User Manual Version 0 1 _a www zennio com...

Страница 2: ...chnical Support https support zennio com 2 CONTENT Content 2 1 Introduction 3 2 Configuration 4 2 1 Configuration 4 2 2 Fan Coil X 4 2 2 1 Valve 7 2 2 2 Fan 11 2 2 3 Initialisation 14 ANNEX I Automati...

Страница 3: ...ts of a four pipe fan coil unit correspond to the cooling and heating functions being therefore both modes available during the device operation The single water circuit of a two pipe fan coil unit on...

Страница 4: ...dependently Refer to the specific application program manual to identify where these boxes are located ETS PARAMETERISATION Figure 1 Fan Coil Configuration Fan Coil X disabled enabled enables the Fan...

Страница 5: ...heating mode Figure 2 Minimum time for mode change Fan coil always on a communication object can be provided for the switch on and the switch off of the fan coil control module as well as its corresp...

Страница 6: ...available for fan coil of 4 Pipes or 2 Pipes with Cooling Heating mode active 0 3600 s 0 1440 min 0 24 h time that will elapse from fan deactivation to the opening of the new mode valve Fan Coil Alwa...

Страница 7: ...t settings for cooling and heating configurations The output control value OV resulting from the scaling function is defined by the following variables 2 2 100 2 1 2 1 1 1 1 2 0 0 1 Input control valu...

Страница 8: ...o With an input value VE of 70 the valve outlet value VS will be 75 Control signal change limits prevents damage to the valve due to small changes in its position and or permanent activation of the va...

Страница 9: ...ng The parameters are the following Control Signal Scaling Minimum Input Value X1 0 100 defines the minimum regulation value to be received from the thermostat that will cause the valve to start openi...

Страница 10: ...t action that caused a change in valve position Notes The parameter minimum change between output signals is not considered if the command involves a change to the maximum value or a closing of the va...

Страница 11: ...et in parameters which of the two control modes must be active after download and also a time out counter to return to automatic mode after a period of time without receiving manual commands On the ot...

Страница 12: ...atic 1 Manual 0 Manual 1 Automatic sets the polarity of the object that enables switching from one control mode to another FCx Fan Manual Automatic as well as its status object FCx Fan Manual Automati...

Страница 13: ...ation but opens the valve the fan will be set to the minimum value Maximum Value 1 100 maximum value allowed so that for any input control value that causes an output higher than this limit the genera...

Страница 14: ...fter start up If the input objects update functionality is enabled the objects on which read requests for update will be sent will be FCx On Off FCx Mode FCx Control Variable Heating Cooling FCx Fan M...

Страница 15: ...start to be sent after the parameterized delay 0 600 s Send Status Object disabled enabled if enabled several checkboxes will be displayed to indicate the objects to be sent On Off disabled enabled Av...

Страница 16: ...orce the fan to stop Whereas if automatic air recirculation in cooling mode is not enabled or the system is operating in heating mode When receiving a control command lower than the value that activat...

Страница 17: ...n and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio...

Отзывы: