Fan Coil ‘Analog’
Technical Support:
10
➢
Maximum Output Value (Y2)
[
0
…
100
] [
%
]: defines the maximum operating
value of the valve, maximum opening position.
Note: If, as a result of a parameterisation error, the minimum value of the control
signal (input or output) is greater than a maximum value, 0% (minimum) and 100%
(maximum) will be taken as control signal scaling range.
Control Signal Change Limits
➢
Minimum Change between Output Signals
[
0…
5
…100
][
%
]: minimum
increase or decrease in the output signal value with respect to the last value
that caused a change in the valve position.
➢
Minimum
Time
between
Output
Signals
[
[
0…
10
…3600][
s
]
/
[0
…1440][min]
]: minimum time that must elapse since the last action that
caused a change in valve position.
Notes:
•
The parameter minimum change between output signals is not
considered if the command involves a change to the maximum value, or
a closing of the valve.
•
These two parameters, minimum change and minimum time between
output signals, must be met simultaneously for the control signal to be
sent to the valve.
Anti-Seize Protection
➢
Anti-Seize Protection
[
disabled
/enabled
]: enables or disables the valve
anti-seize protection function, and with it the objects
"[FCx] Cooling Valve:
Anti-Seize Protection (Status)"
and
"[FCx] Heating Valve: Anti-Seize
Protection (Status)"
, which will take the value "1" when the function is
running or "0" otherwise.
•
Periodicity
[
1…
7
…255
][
day(s)
]: defines the maximum time that the
valve can remain in the same position.
•
Duration
[
1…
5
…255
][
min
]: defines the run time of the anti-seize
protection. During this time the valve will remain in the opposite position.