Fan Coil ‘Analog’
Technical Support:
12
ETS PARAMETERISATION
Figure 6.
Fan Coil - Fan.
Control Mode
[
Automatic
/ Manual / Aut Manual
]. If
“Aut Manual”
is selected, the parameters corresponding to the mode change are displayed:
➢
Mode after ETS Download
[
Automatic
/ Manual
].
➢
Mode Object Polarity
[
0 = Automatic; 1 = Manual
/ 0 = Manual; 1 =
Automatic
]: sets the polarity of the object that enables switching from one
control mode to another
("[FCx] Fan: Manual/Automatic"
), as well as its
status object (
"[FCx] Fan: Manual/Automatic (Status)"
).
➢
Return to Automatic Mode after Period of Time
[
disabled
/enabled
].
Enabling this functionality displays the parameters for its configuration:
•
Manual Control Duration
[
0…
30
…1440
][
min
] / [
0
…
24
][
h
]. If, after this
time, the fan has not received any new manual control command (
"[FCx]
Manual Fan: Speed"
), the automatic control mode will be restored. This