Fan Coil ‘Analog’
Technical Support:
6
ETS PARAMETERISATION
After enabling the
Fan Coil X,
in the "Configuration" tab (see section 2.1), a new tab of
the same name is added to the left tree.
Figure 3.
Fan Coil X - General Configuration.
Type of Fan Coil
[
2 Pipes
/
4 Pipes
].
Mode (
only available for
“2 Pipes” fan coil unit
)
[
Heating
/ Cooling / Cooling +
Heating
].
For fan coil of "4 Pipes" or "2 Pipes" with "C Heating" mode active, there
will be the one-bit object
“[FCn] Mode”
for the selection of the desired mode, as
well as the corresponding status object
“[FCn] Mode (Status)”
.
Mode Change Minimum Time (
only available for fan coil of "4 Pipes" or "2 Pipes"
with "C Heating" mode active
)
[
[
0
…3600][
s
] / [0
…1440][min] / [0…24][h]
]:
time that will elapse from fan deactivation to the opening of the new mode valve.
Fan Coil Always On
[
disabled
/enabled
]: configures the module to maintain the
fan coil control permanently switched on. If disabled, the objects
“
[FCn] On/Off
”
and
“[FCn] On/Off (Status)”
will allow, respectively, to switch on/off the control
and to know its status.
Automatic Air Recirculation in Cooling Mode
[
disabled/
enabled
]:
sets whether
in the Cooling mode the fan should remain on, even when the valve is closed. See
ANNEX I. Automatic Air Recirculation in Cooling Mode.
➢
Fan Speed
[
0…
20
…100
][
%
]: speed that the fan will reach when the air
recirculation is activated. This speed can be modified through the object
"[FCx] Fan: Automatic Air Recirculation Speed"
.