background image

8.0 INSTALLATION AND START-UP

ZEKS Eclipse

TM

 90-5,000ZPB Desiccant Dryers

www.zeks.com

18

8.1 APPLICATION AND CHECK ANALYSIS

To achieve the best dryer performance, carefully check and verify 

that each design and installation requirement outlined below is 

satis

fi

 ed.

The dryer is designed to operate with a compressed air inlet 

temperature ranging from 80ºF to 120ºF and an operating 

pressure ranging between 80 PSI and 150 PSI. The air 

compressor that feeds air to the dryer must be su

  ciently sized 

to meet the process air demand as well as provide the volume 

necessary for desiccant regeneration.

The standard ZPB series heatless desiccant dryer is rated for a 

maximum allowable working pressure of 150 PSIG. If the dryer 

is to be operated at pressures below 80 PSIG, the factory should 

be consulted to verify sizing and con

fi

 guration.

The standard dryer is rated to operate at an inlet temperature 

and pressure of 100ºF @ 100 PSI. Installations with elevated 

inlet air temperatures may require a dryer with greater capacity to 

achieve expected dew point performance. When compressed air 

at lower temperatures is supplied to the dryer, performance will 

be reduced. The compressed air supply must have a minimum 

temperature of 80ºF at the dryer inlet to assure proper dryer 

operation. The operating conditions should be veri

fi

 ed prior to 

dryer installation and operation to ensure it is properly sized. 

The dryer should be installed indoors where the ambient 

temperature does not drop below 50ºF or rise above 120ºF. 

Consult factory for outdoor installations where additional 

provisions may be required for low ambient temperatures.

8.2 LOCATING AND MOUNTING

Using a forklift, lift the dryer only at the lift points identi

fi

 ed with 

labeling. Use care to avoid damage to manifold.

Bolt the dryer to the foundation using the bolt holes provided in 

the base frame. Anchor bolts should project a minimum of 3.5 

inches above the foundation. Refer to SECTION 12, GENERAL 

ARRANGEMENT DRAWINGS, for details.

8.3 PIPING

Pipe the compressed air lines to the dryer inlet and outlet 

connection points. Locate a pre

fi

 lter as close as possible to the 

dryer inlet. Ensure the positioning allows access and room to 

service and maintain the dryer. Refer to the General Arrangement 

drawing.

Note that the wet air inlet is at the dryer’s lower manifold, while 

the dry air outlet is at the dryer’s upper manifold. In situations 

where air supply is required 24 hours a day (where it is 

undesirable to interrupt the air

fl

 ow), a three valve by-pass system 

is recommended to bypass the dryer. To keep pressure drop at 

a minimum, use the fewest number of elbows possible. THE 

BYPASS SHOULD BE USED WHEN TROUBLESHOOTING 

THE AIR COMPRESSOR OR WHEN SERVICING THE ZPB 

DRYER TO PREVENT FLOODING OF THE DESICCANT BED.
When all piping is connected, all joints, including those on the 

dryer, should be soap bubble tested at line pressure to ensure 

no joints have been damaged in transit or during site placement.  

All installed piping must be self-supported. The dryer manifold 

piping cannot be used to support interconnecting piping.

8.4 FILTRATION
NOTE: A Pre

fi

 lter and an After

fi

 lter must be provided in your 

dryer installation.

A coalescing Pre

fi

 lter, mounted before the dryer, will protect 

desiccant beds from contamination by oil, entrained water and 

pipe scale to extend dryer desiccant life and assure proper dryer 

operation. Locate Pre

fi

 lter as close to the dryer as possible. 

Pre

fi

 lter drain must be inspected periodically to ensure proper 

operation. Drain maintenance is not covered in the Warranty.
It is recommended that a mechanical separator with a properly 

functioning drain be installed immediately preceding the Pre

fi

 lter 

to remove bulk liquid and entrained water.
Installation of a Particulate After

fi

 lter mounted after the dryer will 

help eliminate carryover of desiccant dust into the air system.

8.4.1 FILTER DRAIN VALVE (With Factory Installed Filters)

When 90-1,500 SCFM dryers come from the factory with 

fi

 lters 

installed,the Automatic Drains (PN: 24335028) must be checked 

for correct con

fi

 guration prior to pressurization of the dryer:

• Filters must be oriented vertically for proper operation.
• The drain stem must be properly adjusted as follows: 

Twist the drain stem (No. 18 in Figure 2) to set for AUTOMATIC 

(Normal) or MANUAL (Test) operation (See Figure 1 below).

• Twist the stem fully clockwise (when viewed from bottom 

of 

fi

 lter bowl) for AUTOMATIC draining of condensate. 

This is the Normal position.

• Twist the stem fully counter-clockwise (when viewed from 

bottom of 

fi

 lter bowl) for MANUAL draining of condensate 

(Test/Bleed) or if connected to an external drain.

Minimum operating pressure of 22 psig is required for the 

fl

 oat 

that’s within the drain assembly to seat properly. Pressures 

below 22 psig will allow air to escape from the drain. This will 

occur when the compressed air system is being pressurized.

  

!

   NOTICE

The standard dryer is not rated for any gas other than air.

  

!

   NOTICE

ZEKS recommends the mu

  ers be cleaned after initial dryer start-

up to remove desiccant dust that may have been generated during 

dryer shipment. Following the 

fi

 rst 30 minutes of dryer operation, 

de-energize and depressurize the dryer and remove the mu

  ers. 

Disassemble and clean the removable insert inside each mu

  er 

core. Reassemble and reinstall mu

  ers prior to resuming dryer 

operation. To prevent additional clogging, periodic inspection of 

mu

  ers is recommended.

  

!

   NOTICE

All ZPB model dryers must have proper 

fi

 ltration. Liquid water 

and oil must be removed before compressed air enters the 

dryer. Ensure separators, Pre

fi

 lters and drains are in good 

working order.  Failure to do so will void warranty.

Figure 1

AUTOMATIC

MANUAL

Содержание Eclipse 1000ZPB

Страница 1: ...w zeks com Form ZEKS ZPB V0121 ZPB Heatless Purge Desiccant Compressed Air Dryers 90 5 000 scfm NOTICE Those operating the machine or performing maintenance should read and understand the decals posit...

Страница 2: ...ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com...

Страница 3: ...NCLATURE 3 4 RECEIVING AND INSPECTION 3 5 SAFETY AND OPERATION PRECAUTIONS 4 6 PRINCIPLES OF OPERATION 5 7 ALARMS AND INDICATORS 15 8 INSTALLATION INITIAL START UP 18 9 SCHEDULED MAINTENANCE 22 10 TRO...

Страница 4: ...s from the date of equipment start up the Warranty Registration Card must be completed and returned to ZEKS Alternately the Warranty Registration Card may be completed online at www zeks com The total...

Страница 5: ...g fork tongs beneath these rails to avoid damaging piping at the rear of the dryer 4 0 RECEIVING AND INSPECTION NOTICE Nomenclature shown above represents standard price sheet options Other options ar...

Страница 6: ...ons OSHA Heading Descriptions 5 0 SAFETY AND OPERATION PRECAUTIONS ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com 4 NOTICE The user of any air dryer manufactured by ZEKS Compressed Air Solut...

Страница 7: ...ed to atmosphere The second stage of regeneration uses a portion of the dry compressed air expanded to atmospheric pressure to complete the desorption process As depicted in the P ID the compressed ai...

Страница 8: ...cycle is turned o 6 8 PURGESYNC FUNCTION with NEMA 4 Digital Controller option The PurgeSync function enables the dryer to reduce the timing of the purge cycle based on compressed air demand When this...

Страница 9: ...this screen the user can navigate to start stop monitor or alter the dryer Operating Cycle and test dryer functions CONTROLLER BUTTONS AND KEYS i INFORMATION BUTTON Restricted Level access for factory...

Страница 10: ...on Keys to highlight the value that needs to be changed 2 Press the button to change the value to the new setting ZPB Controller Display Display of dryer status program sequence information alarm stat...

Страница 11: ...thin that Step Jog Step Use key to jog the primary steps in the operating sequence TECHNICIAN MODE SCREEN 2 12 Dryer must be turned OFF and system or Control Air Circuit must be pressurized before ini...

Страница 12: ...rigger when measured value exceeds the high Dew Point setting HI DEWPT SETPOINT Value establishes the Alarm trigger point LO DEWPT ALM Choose ON or OFF In certain cases during low flow operation outle...

Страница 13: ...s not rise above this set point during the pressurization cycle for the tower that is designated for drying TECHNICIAN MODE SCREEN 11 12 This screen permits the user to set the Date and Time format th...

Страница 14: ...ce Reminder Interval for key components An alert will be displayed indicating that inspection replacement may be required when the time Interval is reached INLET FILTER Reminder Interval Weeks OUTLET...

Страница 15: ...conds RETRIES Default 3 attempts DELAY Default 10 minutes COMMUNICATIONS SCREEN 2 4 BAUD RATE Press Enter key to highlight field Press to select from preset values DATA BITS Default 8 For information...

Страница 16: ...Fail To Shift option OPERATING STATUS SCREEN 3 7 LT RT Left and Right Tower operating status DRYING or REGENERATING MLC SETPT Status of Moisture Load Control option ON or OFF Indication of Setpoint 40...

Страница 17: ...the towers during the drying and regeneration steps to ensure correct tower pressure values are maintained during each step The tower designated for regeneration should be under 7 PSI during this step...

Страница 18: ...n is true Activate while alarm condition is true Activated while alarm condition is true RECOMMENDED ACTION 1 Troubleshooting Sequence a Verify operation of purge valve Use test button on control air...

Страница 19: ...appear in two weeks Maintenance Alert A pop up ALERT will be displayed to indicate that the Filter Regulator element should be replaced If the user selects NO the reminder will be acknowledged and wi...

Страница 20: ...PREVENT FLOODING OF THE DESICCANT BED When all piping is connected all joints including those on the dryer should be soap bubble tested at line pressure to ensure no joints have been damaged in transi...

Страница 21: ...rotective packaging must not be installed until the dryer has been in operation for 24 hours Color of the Blue Moisture Indicator BMI must appear blue before the Transmitter is installed The dryer War...

Страница 22: ...ller to verify drain functionality after the dryer is placed into operation Drain maintenance or cleaning of system debris is not covered under the ZPB dryer warranty Improper drain maintenance will r...

Страница 23: ...ressurized in order for the main flow valves on the dryer to revert to the default position The status line in the Home screen will display OFF The system will remain pressurized at all times The drye...

Страница 24: ...t 7 days of operation SEMI ANNUAL MAINTENANCE FUNCTIONS Check outlet dew point MLC option only Check Control Air Filter NEMA 1 or Filter Regulator NEMA 4 element and clean or replace as required Repla...

Страница 25: ...t side requires replacement 9 7 DESICCANT CHANGEOUT PROCEDURE When it becomes necessary to replace the desiccant in the towers or on units that are shipped without the desiccant installed observe the...

Страница 26: ...20 38 134 100 34 160ZPB 22 00 29 75 192 150 50 200ZPB 14 00 21 50 236 177 59 250ZPB 23 00 28 00 290 215 75 300ZPB 12 00 21 25 344 258 86 400ZPB 11 00 22 25 470 352 118 500ZPB 27 00 32 00 638 478 160 6...

Страница 27: ...outlet of the dryer is piped to a booster compressor verify that the flow of the booster compressor is below the rated capacity of the dryer Excessive flow will fluidize desiccant bed and result in du...

Страница 28: ...0 Purge Air Flow SCFM Purge Meter Setting psig Dryer Model 160ZPB Purge Pressure Setting 50 psig 26 SCFM Purge Orifice 3 16 0 5 10 15 20 25 30 35 40 45 0 10 20 30 40 50 60 70 Purge Air Flow SCFM Purge...

Страница 29: ...70 80 90 100 110 120 130 0 10 20 30 40 50 60 70 Purge Air Flow SCFM Purge Meter Setting psig Dryer Model 500ZPB Purge Pressure Setting 35 psig 81 SCFM Purge Orifice 3 8 0 10 20 30 40 50 60 70 80 90 10...

Страница 30: ...0 180 210 240 270 300 330 360 0 10 20 30 40 50 60 70 Purge Air Flow SCFM Purge Meter Setting psig Purge Orifice 5 8 1800ZPA Setting 51 psig 292 SCFM 0 50 100 150 200 250 300 350 400 450 500 0 10 20 30...

Страница 31: ...urge Meter Setting psig Purge Orifice 7 8 3300ZPA Setting 47 psig 535 SCFM 0 100 200 300 400 500 600 700 800 900 1000 0 10 20 30 40 50 60 70 Purge Air Flow SCFM Purge Meter Setting psig Purge Orifice...

Страница 32: ...5479 5 7 2 1 7 94 7 57 88 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 3 57 19 7 459 43 1 89 5 79 1 9 9 7 19 7 459 43 1 19 7 5 0 24 39 3 41 8 8 39 11 5479 54 7 43 1 9 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 5...

Страница 33: ...7 94 7 57 88 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 3 57 19 7 459 43 1 19 7 5 0 89 5 79 1 9 9 7 19 7 459 43 1 24 39 3 41 8 8 39 11 5479 1 24 89 7 3 947 5 149 7 8 9 4 1 4 7 4 91 9 4 7 31 9 349 8 2...

Страница 34: ...9 43 1 19 7 5 0 24 39 3 41 8 1 97 1 3 148 7 5 149 7 19 7 1 24 89 7 3 947 54 7 43 1 9 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 5 149 7 8 9 4 1 5 5 4 7 4 91 9 4 7 31 9 59 7 4 91 9 433 9 43 59 7 31 9 433 9 43 G...

Страница 35: ...1 3 472 9 43 1 24 89 7 3 947 5 5 4 7 4 91 9 4 7 31 9 59 7 4 91 9 433 9 43 89 5 79 1 9 9 7 19 7 459 43 1 59 7 31 9 433 9 43 General Arrangement Dryer Models 160ZPB 200ZPB NEMA 4 Drawing No 47597121 34...

Страница 36: ...1 1 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 3 57 19 7 459 43 1 5 7 2 1 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 9 5 9 5 5 5 5 5 24 39 3 41 8 54 7 43 1 9 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 5 149 7 19...

Страница 37: ...459 43 1 19 7 5 0 3 57 19 7 459 43 1 5 7 2 1 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 5 149 7 19 7 7 1 947 5 149 7 8 9 4 1 9 5 9 5 5 5 5 5 24 39 3 41 8 1 24 89 7 3 947 7 31 9 433 9 43 59 5 59 5 5 5...

Страница 38: ...31 8 39 11 5479 94 7 57 88 7 7 1 1 3 57 19 7 459 43 1 5 7 2 1 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 89 5 79 1 9 9 7 19 7 459 43 1 24 39 3 41 8 5 149 7 8 9 4 1 5 149 7 19 7 1 24 89 7 3 947 54 7 43...

Страница 39: ...1 47 9 1 3 472 9 43 8 39 11 5479 94 7 57 88 7 7 1 1 3 57 19 7 459 43 1 5 7 2 1 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 89 5 79 1 9 9 7 19 7 459 43 1 24 39 3 41 8 1 24 89 7 3 947 4 7 4 91 9 9 5 4 7...

Страница 40: ...7 19 7 459 43 1 5 7 2 1 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 54 7 43 1 9 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 5 149 7 8 9 4 1 1 24 89 7 3 947 5 149 7 19 7 1 97 1 3 148 7 4 7 4 91 9 4 7 31 9 General...

Страница 41: ...3 459 43 1 19 7 5 0 7 1 1 3 57 19 7 459 43 1 5 7 2 1 7 259 942 9 7 3 433 9 43 459 43 1 19 7 5 0 1 24 89 7 3 947 4 7 4 91 9 4 7 31 9 General Arrangement Dryer Models 500ZPB 600ZPB NEMA 4 Drawing No 475...

Страница 42: ...14 359 7 4 91 9 433 9 43 359 7 31 9 433 9 43 89 5 79 1 9 9 7 19 7 459 43 1 19 7 5 0 1 9 3 8 55479 8 349 4 7 31 9 4 91 9 459 43 1 1 5 88 8 1 3 9 459 43 1 1 5 88 5 7 892 39 1 4 7 4 91 9 459 43 1 19 7 5...

Страница 43: ...9 942 9 7 3 433 9 43 459 43 1 5 0 9 5 9 5 459 43 1 94 7 38 1 9 43 8 4 3 9 8 431 5 7 14 359 7 4 91 9 433 9 43 359 7 31 9 433 9 43 89 5 79 1 9 9 7 19 7 459 43 1 19 7 5 0 1 9 3 8 55479 8 349 4 7 31 9 4 9...

Страница 44: ...2 1 7 459 43 1 94 7 38 1 9 43 9 8 431 5 7 892 39 1 5 7 14 7 1 3 7 4 91 9 433 9 43 1 9 3 8 55479 8 349 1 3 7 4 91 9 433 9 43 54 7 43 1 9 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 7 1 947 349 8 2 2 2 470 3 57 8...

Страница 45: ...8 39 11 5479 1 24 89 7 3 947 5 149 7 8 9 4 1 9 5 9 5 5 7 2 1 7 459 43 1 94 7 38 1 9 43 9 8 431 5 7 892 39 1 5 7 14 7 1 3 7 4 91 9 433 9 43 1 9 3 8 55479 8 349 1 3 7 4 91 9 433 9 43 349 8 2 2 2 470 3...

Страница 46: ...9 9 5 9 5 459 43 1 94 7 38 1 9 43 9 8 431 1 9 94 7 7 3 1 9 1 24 89 7 3 947 5 149 7 8 9 4 5 149 7 19 7 7 9 94 7 7 3 1 9 1 7 1 947 349 8 2 2 2 470 3 57 88 7 5 8 8 9 7 1 1 8 99 3 5 8 5 149 7 1 3 8 349 8...

Страница 47: ...7 892 39 1 7 1 3 7 4 91 9 433 9 43 1 3 7 31 9 433 9 43 5 149 7 19 7 7 1 947 5 149 7 8 9 4 1 9 5 9 5 459 43 1 94 7 38 1 9 43 9 8 431 349 8 2 2 2 470 3 57 88 7 5 8 8 9 7 1 1 8 99 3 5 8 5 149 7 1 3 8 34...

Страница 48: ...59 43 1 94 7 38 1 9 43 8 4 3 9 8 431 5 7 14 5 7 892 39 1 1 9 3 1 8 8 349 9 5 94 7 57 88 7 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 1 24 89 7 3 947 5 149 7 8 9 4 1 5 149 7 19 7 7 1 947 349 8 2 2 2 470 3 57 88...

Страница 49: ...1 I 4 7 31 9 8 39 7 3 5479 4 7 31 9 24 39 3 41 8 I 4 7 31 9 1 3 7 31 9 433 9 43 9 5 I 4 7 4 91 9 7 1 1 459 43 1 94 7 38 1 9 43 8 4 3 9 8 431 5 7 14 5 7 892 39 1 1 9 3 1 8 8 349 9 5 349 8 2 2 2 470 3 5...

Страница 50: ...4 7 43 1 9 9 5 9 5 I 4 7 31 9 8 39 7 3 5479 4 7 31 9 459 43 1 94 7 38 1 9 43 8 4 3 9 8 431 5 7 892 39 1 1 9 3 8 55479 8 349 4 349 1 9 7 7 57 88 7 9 43 1 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 5 149 7 8 9 4...

Страница 51: ...7 19 7 7 1 947 94 7 57 88 7 24 39 3 41 8 8 39 11 5479 1 24 89 7 3 947 5 149 7 8 9 4 1 9 5 9 5 I 4 7 31 9 8 39 7 3 5479 4 7 31 9 459 43 1 94 7 38 1 9 43 8 4 3 9 8 431 5 7 892 39 1 1 9 3 8 55479 8 349 4...

Страница 52: ...5 I 4 7 31 9 459 43 1 94 7 38 1 9 43 8 4 3 9 8 431 5 7 14 5 7 892 39 1 1 9 3 1 8 8 349 4 349 1 9 7 9 5 7 57 88 7 9 43 1 1 9 94 7 7 3 1 9 7 9 94 7 7 3 1 9 5 149 7 8 9 4 5 149 7 19 7 1 7 1 947 349 8 2...

Страница 53: ...1 8 8 349 4 349 1 9 7 9 5 7 57 88 7 9 43 1 12 0 GENERAL ARRANGEMENT ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com General Arrangement Dryer Model 5000ZPB NEMA 4 Drawing No 47597130 A 51 349...

Страница 54: ...am Dryer Model and Serial Number must be provided when ordering 2 23702244 Display Board Panel 3 634083 Overlay Controller 4 47587161001 Power Supply 5VDC 24VDC 5 38052411 Transducer Cable 5 Ft Lead F...

Страница 55: ...ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com 13 0 WIRING DIAGRAM Wiring Diagram NEMA 4 Standard Drawing No 47595562 53...

Страница 56: ...ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com 54 13 0 WIRING DIAGRAM Wiring Diagram NEMA 4 MLC Drawing No 47595563...

Страница 57: ...OLERANCES ARE CAD GENERATED DRAWING PROPRIETARY NOTICE NOTICE THIS DRAWING EMBODIES A CONFIDENTIAL PROPRIETARY DESIGN OWNED BY ZEKS AND ALL PATENT RIGHTS AND DESIGN MANUFACTURING THE SAME ARE EXPRESSL...

Страница 58: ...VE FV 2B RIGHT TOWER PURGE VALVE FV 1C LEFT TOWER OUTLET CHECK VALVE FV 2C RIGHT TOWER OUTLET CHECK VALVE FV 1P LEFT TOWER PURGE CHECK VALVE FV 2P RIGHT TOWER PURGE CHECK VALVE FV 4A LEFT TOWER INLET...

Страница 59: ...IN GAUGE FO 1 PURGE ORIFICE FO 4 REPRESSURIZATION ORIFICE NOTE 3 FV 1A LEFT TOWER INLET VALVE FV 2A RIGHT TOWER INLET VALVE FV 1B LEFT TOWER PURGE VALVE FV 2B RIGHT TOWER PURGE VALVE FV 1C LEFT TOWER...

Страница 60: ...IGHT TOWER PURGE MUFFLER FR 1 CONTROL AIR FILTER WITH REGULATOR AND BUILT IN GAUGE FLT 2 PREFILTER HIGH EFFICIENCY NOTE 4 FLT 3 AFTERFILTER DUST PARTICULATE NOTE 4 FO 1 PURGE ORIFICE FO 4 REPRESSURIZA...

Страница 61: ...SURIZATION ORIFICE NOTE 3 FV 1A LEFT TOWER INLET VALVE FV 2A RIGHT TOWER INLET VALVE FV 1B LEFT TOWER PURGE VALVE FV 2B RIGHT TOWER PURGE VALVE FV 1C LEFT TOWER OUTLET CHECK VALVE FV 2C RIGHT TOWER OU...

Страница 62: ...FFLER FR 1 CONTROL AIR FILTER WITH REGULATOR AND BUILT IN GAUGE FLT 2 PREFILTER HIGH EFFICIENCY NOTE 3 FLT 3 AFTERFILTER DUST PARTICULATE NOTE 3 FO 1 PURGE ORIFICE FO 4 REPRESSURIZATION ORIFICE NOTE 2...

Страница 63: ...ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com 61 14 0 FLOW DIAGRAM Flow Diagram 1800 2700 ZPB NEMA 4 Drawing No 47634360 A...

Страница 64: ...ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com 62 14 0 FLOW DIAGRAM Flow Diagram 3300 5000 ZPB NEMA 1 Drawing No 47634364 A...

Страница 65: ...ZEKS EclipseTM 90 5 000ZPB Desiccant Dryers www zeks com 63 14 0 FLOW DIAGRAM Flow Diagram 3300 5000 ZPB NEMA 4 Drawing No 47634361 A...

Страница 66: ...ENT AFTERFILTER PARTIC EC110G EC135G EC235G EC235G EC290G 1 1 1 2 DPI 2 3 GAUGE DIFF PRESSURE FILTER 634658 634658 634658 634658 634658 2 PI 1 2 3 GAUGE PURGE TOWER PRESS 680572 680572 680572 680572 6...

Страница 67: ...C350H EC470H EC600H EC600H 1 1 1 2 FLT 3 ELEMENT AFTERFILTER PARTIC EC350G EC470G EC600G EC600G 1 1 1 2 DPI 2 3 GAUGE DIFF PRESSURE FILTER 634658 634658 634658 634658 2 PI 1 2 3 GAUGE PURGE TOWER PRES...

Страница 68: ...920H EC1080H EC1350H EC1600H 1 1 1 2 FLT 3 ELEMENT AFTERFILTER PARTIC EC920G EC1080G EC1350G EC1600G 1 1 1 2 DPI 2 3 GAUGE DIFF PRESSURE FILTER 634658 634658 634658 634658 2 PI 1 2 3 GAUGE PURGE TOWER...

Страница 69: ...C EF600G 3 EF600G 4 EF600G 5 EF600G 6 EF600G 7 EF600G 10 Qty 1 Set 1 Set 2 Sets DPI 2 3 GAUGE DIFF PRESSURE FILTER 633353 633353 633353 633353 633353 633353 2 PI 1 2 3 GAUGE PURGE TOWER PRESS 631324 6...

Страница 70: ...O N O 47607077006 47607078006 47590672001 VALVE ANGLE 2 P O N C 47607077007 47607078007 47607080002 47590670001 VALVE ANGLE 2 P O N O 47607077008 47607078008 47590671001 VALVE ANGLE 2 P O N O 47607077...

Страница 71: ...705001 SP Blue Moisture Indicator CONTROL AIR SOLENOID and FILTER REGULATOR ASSEMBLY Optional Dew Point Transmitter not shown PART NO DESCRIPTION 633671 Cable Transmitter 633691 Resistor 250 OHM R3 o...

Страница 72: ...64 00 51 25 87 62 2 424 1 270 1500ZPB 1 500 1 200 243 4 NPT 78 00 54 76 80 00 2 974 1 600 1800ZPB 1 800 1 440 292 4 NPT 84 00 60 62 91 88 3 905 2 000 2100ZPB 2 100 1 680 340 4 NPT 84 00 60 62 91 88 4...

Страница 73: ...1302 Goshen Parkway West Chester PA 19380 Phone 610 692 9100 800 888 2323 Fax 610 692 9192 Web www zeks com...

Отзывы: