39
■
Removal of residual moisture from the room
■
Correct operation of supply and extract air fans control of their operation.
Minimum access level: Service
Access path to the CO₂ threshold settings:
Manual / Auto
Settings
Configuration
Access rights
Ctrl CO2 / VOC
Fire function
Moisture regulation
Exchanger de-icing
Ctrl CO2 / VOC active:
If pgr on
Type:
fans
Duration min:
20
min
Sequential
Speed 1/2 800 ppm
Speed 1/1 1000 ppm
Diff: 160 ppm
Minimum access level: Operator
Access path to the fan speed parameters:
Temperature control
Ventilation control
Time settings
Access rights
Frequency control
VAS manual
Outlet: 0 %
Frequency control
VAS manual
Output 1/1:
70 %
Output 1/2:
50 %
Frequency control
VAR manual
Output 1/1:
70 %
Output 1/2:
50 %
Frequency control
VAR manual
Outlet: 0 %
Zehnder Eversky