8.5.3. Installation of the unit on a false ceiling
The unit can be semi-recessed in a false ceiling (installation (A)) up to 10 mm above the supply grille frame.
(A) Mounting in contact with the ceiling
(B) Offset ceiling mounting
The unit can also be offset from the ceiling (installation (B)).
In this case, remove the 4 screws (E) M10x70 and replace them with an M10 threaded rod. Allow the threaded rod to
protrude 70 mm below the bracket.
Ensure that the fixing of the threaded rods in the ceiling is strong enough to support :
■
The weight of the unit itself and any options fitted to it
■
The installation loads
■
The operating/maintenance loads
8.6. Access to the inside of the unit
The Zehnder Eversky ventilation unit has 3 independent, recessed, hinged doors for access to the interior.
To close a door:
1 Push the door until it presses against the seal
towards the hinges
2 Raise the door upwards
3 Turn the bolts in the direction of the arrows