8. Technical specifications
Description
Comfofond-L 350
Comfofond-L 550
Mass Comfofond-L
42 kg
42 kg
Unit dimensions (l x b x h)
476 x 551 x 760 mm
476 x 551 x 760 mm
Air inlet dimensions
180 mm
180 mm
Air outlet dimensions
160 mm
180 mm
Outdoor temperature operating area
-22ºC to 45ºC
-22ºC to 45ºC
IP class
44
44
Power supply
220/230V AC, 50/60Hz, 1 phase
220/230V AC, 50/60Hz, 1 phase
Maximum power consumption
0.58 A
0.58 A
Power consumption nominal
0.20 A
0.20 A
Energy consumption maximum
70 W
70 W
Energy consumption nominal
46 W
46 W
Energy consumption minimum setting
5 W
5 W
Heating capacity
1800 W
2500 W
Cooling capacity
2000 W
3000 W
Maximum sound capacity
40 dB(A)
40 dB(A)
Ideal fluid pressure
1.5 bar
1.5 bar
Fluid volume Comfofond-L
+/- 2 l
+/- 2 l
Fluid flow rate
6-8 l/min.
8-10 l/min.
Fluid composition
30%-50% ethylene glycol
water mixture
30%-50% ethylene glycol
water mixture
Fluid connections
¾” conical male-threaded
¾” conical male-threaded
Condensation drain connection
1¼” male-threaded with
32 mm adapter
1¼” male-threaded with
32 mm adapter
Colour
RAL7035
RAL7035
Linear adjustment of the energy consumption is possible
8.1 Brine loop dimensions
The Comfofond-L terrestrial heat collector (recommendations)
Type
Pipe
Fluid volume per 10
metre pipe [l]
Minimum length pipe
in solid ground [m]
Minimum length
pipe in sandy
ground [m]
Comfofond-L 350
25/20.4 PE
3,3
65
130
Comfofond-L 550
32/26 PE
5,3
100
200
Содержание ComfoFond-L
Страница 8: ...EN 4 3 1 Dimensional sketch Comfofond L 350 L Elevation P...
Страница 9: ...EN 5 3 2 Dimensional sketch Comfofond L 350 R Elevation P...
Страница 10: ...EN 6 3 3 Dimensional sketch Comfofond L 550 L Elevation P...
Страница 11: ...EN 7 3 4 Dimensional sketch Comfofond L 550 R Elevation P...
Страница 31: ...EN 27 II Maintenance log Date Activity Initials...