9 - EN
ComfoAir 350 HL (high air volumes)
Position
Ventilation capacity
Power
Low Setting
125 m
3
/h at 25 Pa
27 W
Medium Setting
225 m
3
/h at 150 Pa
105 W
High Setting
300 m
3
/h at 230 Pa
196 W
Maximum
325 m
3
/h at 235 Pa
243 W
Position
Ventilation capacity
Current
Low Setting
125 m
3
/h at 25 Pa
0.21 A
Medium Setting
225 m
3
/h at 150 Pa
0.81 A
High Setting
300 m
3
/h at 230 Pa
1.42 A
Maximum
325 m
3
/h at 235 Pa
1.77 A
Electricity
Power supply
230/50 V/Hz
Cos.phi
0,50 - 0,60
Connecting Power
1,59 kW
Maximum Power Pre-heater
1,35 kW
Leakage current
<1mA
Supply fan noise level (at 0 m)
Position
Ventilation capacity
Sound power
Low Setting
125 m
3
/h at 25 Pa
54 dB(A)
Medium Setting
225 m
3
/h at 150 Pa
67 dB(A)
High Setting
300 m
3
/h at 230 Pa
73 dB(A)
Maximum
325 m
3
/h at 235 Pa
75 dB(A)
Exhaust fan noise level (at 0 m)
Position
Ventilation capacity
Sound power
Low Setting
125 m
3
/h at 25 Pa
45 dB(A)
Medium Setting
225 m
3
/h at 150 Pa
55 dB(A)
High Setting
300 m
3
/h at 230 Pa
59 dB(A)
Maximum
325 m
3
/h at 235 Pa
61 dB(A)
General Specifications
HE Exchanger Material
Polystyrene
Interior Material
(E)PP / PA / PC
Thermal Yield
95%
Mass
39 kg