EN - 16
Menu P5
¨
Setting additional programmes
Additional programme values
Submenu
Description
Minimum
Maximum
General
Reset
P50
Activation of the open fire programme.
0 (= No)
1 (= Yes)
0
P51
Confirming the presence of
a Preheater element
0 (= No)
1 (= Yes)
0
Only change if a preheater element is installed afterwards or a general reset is given.
P52
Setting the Preheater programme.
■
0; Guaranteed protection.
■
1; High protection.
■
2; Nominal protection.
■
3; Economy.
0
3
2
In
guaranteed
protection
mode
the Preheater element is switched on soonest; this level offers the best guarantee of balanced
ventilation. Vice versa, in
economy
mode
the Preheater element switches on at the last possible moment; balanced ventilation is
not guaranteed in this mode.
When commissioning the ComfoAir, the Preheater programme can usually be left at level 2:
nominal
mode
(factory setting). In
areas with frequent cold spells in winter (frequent periods of -10°C or lower), level 1 should be selected:
high
protection
or even
level 0:
guaranteed
protection
.
P54
Confirming the presence of a bypass.
0 (= No)
1 (= Yes)
1
The standard ComfoAir configuration includes a bypass. Therefore, leave the value at ‘1’.
P56
Setting the required air volume in the house.
■
nL: ”normal air volume”.
■
HL: "high air volume".
nL
HL
HL
Setting the air volume is the starting point for programming the air specifications and setting the fans.
P57
Setting the ComfoAir type.
■
Li = ”Left-hand version”.
■
Re = ”Right-hand version”.
Li
Re
Li
With delivery the ComfoAir is correctly pre-programmed at the factory.
After an general reset the pre-programming is lost and the setting must be reset.
The right setting is mentioned on the identification plate on top of the ComfoAir.
P58
n/a
0
1
0
P59
Confirming the presence of an enthalpy exchanger.
■
0; Enthalpy exchanger not fitted
■
1; Enthalpy exchanger with RH sensor.
■
2; Enthalpy exchanger without RH sensor.
0 (= No)
2 (= Yes)
0
Only an enthalpy exchanger without RH sensor can be fitted.
Menu P6
¨
Setting additional programmes
Additional programme values
Submenu
Description
Minimum
Maximum
General
Reset
P60
Confirming the presence of a geothermal heat exchanger.
■
0; Geothermal heat exchanger not fitted
■
1; Geothermal heat exchanger fitted
■
3; Geothermal heat exchanger unregulated.
0 (= No)
3 (= Yes)
0
Only an unregulated geothermal heat exchanger can be fitted.