21 - EN
A5
Malfunction in the
bypass motor
Release the front panel
by removing the protection
caps and unscrewing
the screws.
Remove the cover of
the electronic box by
pressing in the 2 click
connectors.
Activate the self-test.
(P76 on 1)
Did the
bypass motor
run
Yes
Disconnect the
power from
the ComfoAir.
Replace the
control circuit
board.
Remove the
motor
Disconnect the
power from
the ComfoAir.
Is the cog of
the motor
defective?
Yes
No
Replace the cog
of the motor
Replace the
motor
Was there
8 VDC power
present on the
motor?
Yes
Disconnect the
power from
the ComfoAir.
Replace the
motor
No
No
A6
Malfunction
Reset the unit
(P74 on1)
Set P51 to “0”.
EA2
Malfunction
Reset the unit
(P74 on 1)
Set P59 correctly
Risk of electrocution.