23 - EN
Risk of electrocution.
EA2
No communication
between the
enthalpy sensor and
the ComfoAir
Disconnect the power
from the ComfoAir.
Are the
connections
at the
ComfoAir
correct?
Reconnect the
enthalpy sensor.
Yes
Is
P59 set to
the correct
value?
Yes
No
Set P59 to the correct
value.
Reset the unit
(P74 on 1)
Install all parts in
reverse order.
Reconnect the
power to the
ComfoAir.
No
Replace the
connection panel.
Release the front panel
by removing the protection
caps andunscrewing
the screws.
Remove the cover
of the electronic box
by pressing in
the 2 click connectors.