EN - 24
Reconnect the
ComfoAir to the
CC Ease panel.
Yes
No
Check the cable
between the
CC Ease panel
and ComfoAir.
Is
something
wrong with
the cable?
Yes
No
Replace the
cable.
Replace the
CC Ease panel.
Is a
signal present on
the connection
panel?
No
Yes
Reconnect the
power to the
ComfoAir.
Disconnect the
power from
the ComfoAir.
Install all parts in
reverse order.
Reconnect the
power to
the ComfoAir.
Install all parts in
reverse order.
Reconnect the
power to
the ComfoAir.
Install all parts in
reverse order.
Reconnect the
power to the
ComfoAir.
Disconnect the
power from the
ComfoAir.
Replace the
connection panel.
Are the
connections
at the
ComfoAir
correct?
Disconnect the power
from the ComfoAir.
Are the
connections
at the CC
Ease panel
correct?
Reconnect the
CC Ease panel to
the ComfoAir.
Reconnect the
power to the
ComfoAir.
Yes
No
NC
No communication
between the CC Ease
panel and the ComfoAir
Release the front panel
by removing the protection
caps andunscrewing the screws.
Remove the cover of the
electronic box by pressing
in the 2 click connectors.
Risk of electrocution.
The connections
of the CC Ease
panel must be
crossed.
(Rx must be
connected to Tx)
The connections of the CC
Ease panel must be crossed.
(Rx must be connected to
Tx)
The connections of
the CC Ease panel
must be crossed.
(Rx must be
connected to Tx)