EN - 16
Menu P7
¨
Reading malfunctions (and system information)
(Malfunction) information values
Submenu
description
Minimum
Maximum
General
reset
P75
General reset.
•
Press
"OK" on the display or press
“
” on the CC-Ease panel for at
least 5 seconds to carry out a general
reset.
All original software settings are re-
stored following a general reset.
0
1
(= activate)
0
Note:
After a general reset, the ComfoAir will ask you to reset the “nL / HL” (see P56) settings.
Following a general reset, all settings and programmes need to be checked and set to the
right value.
P76
Self-testing the ComfoAir
0
1
(= activate)
0
• The LED's on the display will start blinking.
• The ComfoAir will run at maximum Rotation Per Minute (RPM).
• The bypass valve will open and close.
P77
Resetting filter dirty counter
0
1
(= activate)
0
Note:
This resets the counter that triggers a dirty filter alert on the ComfoAir. This allows the filter to be cleaned or
replaced when the dirty filter alert appears.
Menu P8
¨
Setting the RF input and digital inputs (0-10V)
Analogue input values
Submenu
description
Minimum
Maximum
General reset
810
Analogue input 1 0= not fitted 1= fitted
0
1
0
811
0= controlling 1= programming (analogue input 1)
0
1
0
812
set point analogue input 1 (programming)
0
100
50
813
min. setting analogue input 1
0
99
0
814
max. setting analogue input 1
0
100
100
815
0=positive analogue input 1 1=negative setting ana-
logue input 1
0
1
0
816
read-out analogue input 1
0
100
-
820
Analogue input 2 0= not fitted 1= fitted
0
1
0
821
0= controlling 1= programming (analogue input 2)
0
1
0
822
set point analogue input 2 (programming)
0
100
50
823
min. setting analogue input 2
0
99
0
824
max. setting analogue input 2
0
100
100
825
0=positive analogue input 2 1=negative setting ana-
logue input 2
0
1
0
826
read-out analogue input 2
0
100
-
850
RF input 1 0= not fitted 1= fitted
0
1
0
851
0= controlling 1= programming (RF input 1)
0
1
0
852
set point RF input 1 (programming)
0
100
50
853
min. setting RF input 1
0
99
0
854
max. setting RF input 1
0
100
100
855
0=positive RF input 1 1=negative setting RF input 1 0
1
0
856
Read-out RF input
0
100
-