7 - EN
The ComfoAir is supplied in the following types:
Type
ComfoAir 160 Basic R
ComfoAir 160 Basic R ERV
ComfoAir 160 R Luxe
ComfoAir 160 R Luxe ERV
Meaning of the suffi xes:
* R
= Right version
* ERV = Contains a enthalpy exchanger by default.
CC Ease panel (optional) can be ordered separately.
2.5.3 Rework Right to Left version
1. Remove the front panel by fi rst removing the 6 protective
caps (A) then the screws.
2. Remove the protection cap in the bottom of the front panel
(B).
3. Place the removed protection cap in the old display hole.
4. Push out the foam behind the new gap and place it behind
the moved protection cap.
A
A
B
5. Release the back panel and the mounting brackets by un-
screwing the 4 screws.
6. Remove the cover of the electronic box by pressing in the
2 click connectors (C).
7. Remove the display connector from the control PCB.
8. Release the display by unscrewing the 2 screws (D)
9. Place the removed display on the back side of the Com-
foAir.
10. Connect the display connector again.
11. Place the cover of the electronic box back.
12. Remove the 2 fi lters (E) from the ComfoAir.
13. Place the back panel and the mounting brackets on the
old front side.
14. Place the removed fi lters in the new front side of the Com-
foAir.
15. Place the front panel on the old back side.
2.5.4 Connecting the power cord
1. Release the electronic cover by unscrewing the 4 screws
(F).
2. Carefully pull up the electronic cover
3. Pull the power cord thru the hole marked "230V".
4. Connect the Blue wire to the connector marked "N".
5. When present connect the Brown wire to the connector
marked "H".
6. When present connect the Black wire to the connector
marked "M".
7. Connect the Gray wire to the connector marked "L".
8. Connect the Green/Yellow wire to the connector marked
"
"
Make sure the earth wire (Green/Yellow) is at
least 40 mm longer than the other connected
wires.
9. Carefully place the electronic cover back.
10 Fasten the electronic cover with the 4 removed screws.
2.6 Mounting of the ComfoAir
The ComfoAir can be mounted two ways:
• On the ceiling;
• On the wall.
2.6.1 Mounting on the ceiling
804
C
2%
Mount the ComfoAir to a ceiling with a minimum mass
of at least 200 kg/m
2
.
1. Seal off the existing condensation drain.
2. Remove the front panel by fi rst removing the 6
protective caps (A) then the screws.
A
Содержание ComfoAir 160
Страница 1: ...ComfoAir 160 Installer manual...
Страница 4: ......
Страница 32: ...EN 28 2 12 Wiring diagram ComfoAir 160...
Страница 34: ...EN 30...
Страница 35: ...31 EN...