Identification: MD-AL-GI-00
Rev. 1.2 07.06.21 - Application: GID
Connext User Manual
Rev. 2.2 10/01/2023
15.
Appendix B
–
Meter settings
The power cables for phases R, S, T and the neutral cable (N) are connected to the meter via pints 2,
5, 8 and 10, respectively. The CTs for measuring the current are connected:
-
R-phase measurement with the terminals connected to PIN 1 (red wire) and PIN 3 (black wire).
-
S-phase measurement with the terminals connected to PIN 4 (red wire) and PIN 6 (black wire).
-
T-phase measurement with the terminals connected to PIN 7 (red wire) and PIN 9 (black wire).
Position the sensors according to the direction on the sensor (arrow).
ATTENTION: attach the CT sensors to the phases only after they have been connected to the Meter.
Connect the Meter and Connext via the RS485 serial port. On the Meter side, this port is identified
by PINs 24 and 25, on the Connext System by PINs 9 and 10, respectively.
Figure 72 - Meter connections