JOHNSON CONTROLS
39
SECTION 4 – INSTALLATION
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
4
TABLE 4 -
REFRIGERANT LINE CONNECTIONS
MODEL
NUMBER TONS
SYSTEM
NUMBER
REFRIGERANT
LINE CONNECTION
SUCTION LINE
LIQUID LINE
SUCTION LIQUID
COPPER
TYPE L
INCHES OD
VELOCITY
@ NOMINAL
CAPACITY
IN FPM
NOMINAL
TONS UN-
LOADED
COPPER
TYPE L
INCHES OD
0248YE
81.2
1
2.7
1.1
2-5/8
1656
13.5
1-1/8
2
2.7
1.1
2-5/8
1656
3.5
1-1/8
0278YE
84.3
1
2.7
1.1
2-5/8
1818
14.9
1-1/8
2
2.7
1.1
2-5/8
1572
13.2
1-1/8
0298YE
91.1
1
2.7
1.1
2-5/8
1812
14.9
1-1/8
2
2.7
1.1
2-5/8
1896
14.9
1-1/8
0308YE
98.5
1
2.7
1.1
2-5/8
1896
14.9
1-1/8
2
2.7
1.1
2-5/8
1896
14.9
1-1/8
0338YE
111.5
1
2.7
1.1
2-5/8
1812
14.9
1-1/8
2
2.7
1.1
2-5/8
2598
33.6
1-1/8
0408YE
131.5
1
2.7
1.1
2-5/8
2658
32.8
1-1/8
2
2.7
1.1
2-5/8
2658
32.8
1-1/8
0468YE
145.3
1
3.1
1.4
3-1/8
2790
31.3
1-3/8
2
2.7
1.1
2-5/8
1926
14.9
1-1/8
0498YE
158.3
1
3.1
1.4
3-1/8
2658
30.7
1-3/8
2
2.7
1.1
2-5/8
2656
33.1
1-1/8
Refrigerant Piping Notes
1. Based on R-410A at the nominal capacity of the unit or system, an ambient temperature of 95°F (35°C) and a suction temperature of 45°F
(7.2°C).
2. Suction line sizes were calculated based on a nominal maximum pressure drop to 3 PSI/100 ft. (20.7 kPa/30.5 m). When calculating suction
line pressure drop for a specific application, it should be noted that system capacity decreases as suction line pressure drop increases.
4. Nominal Tons (KW) Unloaded is based on one compressor (per system) operating at design conditions.
5. Based on minimum compressor staging for the given pipe size, a double suction riser should be used to ensure proper oil return to the com-
pressor on all vertical suction risers. Oil returning up the riser moves up the inner surface of the pipe and depends on the mass velocity of
the refrigerant vapor at the wall surface to move the oil up the vertical rise.
6. Hot gas bypass lines are typically 7/8” for lines up to 40 feet and 1-1/8” for lines over 40 feet in length (12 meters). The field connections sizes
are 7/8” for the optional factory mounted hot gas bypass valve. Note: Hot gas bypass is only available for refrigerant system number 1.
7. For more information, please refer to either the York DX Piping Guide (Form 050.40-ES2) or the ASHRAE Refrigertion Handbook.
Содержание YLUA0248 Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 65: ...JOHNSON CONTROLS 65 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13901 ...
Страница 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 71: ...JOHNSON CONTROLS 71 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13239 ...
Страница 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 75: ...JOHNSON CONTROLS 75 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13993A 1 ...
Страница 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...