SECTION 8 – UNIT OPERATION
BAS/EMS DISCHARGE AIR TEMPERATURE
RESET USING A VOLTAGE OR CURRENT
SIGNAL
The Remote Reset Option allows the Control Center of the
unit to reset the discharge air temperature setpoint using a
0 - 10VDC input, or a 4-20mA input connected to
XTBC1 terminals A- and A+. Whenever a reset is
called for, the change may be noted by pressing the
Cooling Setpoints key twice. The new value will be
displayed as “REM SETP = XXX °F.”
If a
0 - 10VDC
signal is supplied, it is applied to ter-
minals A+ and A-, and
jumper JP1 on the I/O board
must be inserted between pins 2 and 3.
To calculate
the reset discharge air temp setpoint for values between
0VDC and 10VDC use the following formula:
Setpoint = Local Discharge Air Temp Se °Reset
°
Reset = (DC voltage signal) x (*Max Reset Value)
10
Example:
Local Discharge Air Temp Setpoint = 45 °F (7.22
°C)
*Max Reset Value = 20 °F (11.11 °C)
Input Signal = 6VDC
(English)
°
Reset = 6VDC x 20 °F = 12
°F Reset
10
New Setpoint = 45 °F + 12 °F = 57 °F
(Metric)
°
Reset = 6VDC x 11. 11 °C = 6.67 °C Reset
10
New Setpoint = 7.22 °C + 6.67 °C = 13.89 °C
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset”
setpoint value described in the programming section under Cooling
Setpoints. Programmable values are from 2 °F to 40 °F (1.11 °C
to 11.11 °C).
** Note: The Suction Pressure Setpoints are not remotely
resettable.
If a
4-20mA signal is supplied,
it is applied to termi-
nals A+ and A- and
jumper JP1 on the I/O board
must be installed between pin 1 and 2
. To calculate
the discharge air temp setpoint for values between 4mA
and 20 mA use the following formula:
Setpoint = Local Discharge Air Temp Se
°Reset
°Reset = (mA signal - 4) x (*Max Reset Value)
16
Example:
Local Discharge Air Temp Setpoint = 45° (7.22
°C)
*Max Reset Value = 10 °F (5.56 °C)
Input Signal = 12 mA
(English)
°Reset = 8mA x 10 °F = 5 °F Reset
16
Setpoint = 45 °F + 5 °F = 50 °F
(Metric)
°Reset = 8mA x 5.56 °C = 2.78 °C Reset
16
Setpoint = 7.22 °C + 2.78 °C = 10.0 °C
A 240-24 Volt Ratio Transformer (T3) is
used to derive nominal 12 volt output from
the 120 volt supply.
Содержание YLUA0248 Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 65: ...JOHNSON CONTROLS 65 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13901 ...
Страница 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 71: ...JOHNSON CONTROLS 71 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13239 ...
Страница 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 75: ...JOHNSON CONTROLS 75 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13993A 1 ...
Страница 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...