JOHNSON CONTROLS
133
SECTION 8 – UNIT OPERATION
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
8
LOAD LIMITING
Load Limiting is a feature that prevents the unit from
loading beyond the desired value. 2 and 4 compres-
sor units can be load limited to 50%. This would allow
only 1 compressor per system to run. 3 and 6 compres-
sor units can be load limited to 33% or 66%. The 66%
limit would allow up to 2 compressors per system to
run, and the 33% limit would allow only 1 compressor
per system to run. Five-compressor units may be load
limited to 40% (1 compressor per system runs) or 80%
(up to 2 compressors per system) are permitted to run.
No other values of limiting are available.
There are two ways to load limit the unit. The first is
through remote communication via an ISN.
A second way to load limit the unit is through closing
contacts connected to the Load Limit (XTBC1 – ter-
minals 13-21) and PWM inputs (XTBC1 – terminals
13-20). Stage 1 of load limiting involves closing the
Load Limit input. Stage 2 of load limiting involves
closing both the Load Limit and PWM inputs. The
first stage of limiting is either 80%, 66% or 50%, de-
pending on the number of compressors on the unit.
The second stage of limiting is either 40% or 33% and
is only available on 3, 5 & 6 compressor units. Table
25 shows the load limiting permitted for the various
numbers of compressors.
Simultaneous operation of Remote Load
Limiting and EMS-PWM Temperature
Reset (described on following pages)
cannot occur.
COMPRESSOR RUN STATUS
Compressor run status is indicated by closure of con-
tacts at XTBC2 – terminals 25 to 26 for system 1 and
XTBC2 – terminals 27 to 28 for system 2. The respec-
tive contact will close anytime a compressor is running
in that particular system.
The compressor Run Status contacts can also be used
to cycle the evaporator fan contactor with the compres-
sors.
ALARM STATUS
System or unit shutdown is indicated by normally-
open contacts opening whenever the unit shuts down
on a unit fault, or locks out on a system fault. System
1 alarm contacts are located at XTBC2 - terminals 29
to 30. System 2 alarm contacts are located at XTBC2 -
terminals 31 to 32. The alarm contacts will close when
conditions allow the unit to operate.
COMPRESSORS
IN UNIT
STAGE 1
STAGE 2
2
50%
-
3
66%
33%
4
50%
-
5
80%
40%
6
66%
33%
TABLE 23 -
COMPRESSOR OPERATION – LOAD
LIMITING
Содержание YLUA0248 Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 65: ...JOHNSON CONTROLS 65 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13901 ...
Страница 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 71: ...JOHNSON CONTROLS 71 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13239 ...
Страница 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 75: ...JOHNSON CONTROLS 75 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13993A 1 ...
Страница 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...