JOHNSON CONTROLS
144
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
SECTION 9 – SERVICE AND TROUBLESHOOTING
TROUBLESHOOTING
TABLE 31 -
TROUBLESHOOTING
CONT’D
PROBLEM
CAUSE
SOLUTION
NO DISPLAY ON PANEL.
UNIT WILL NOT OPERATE
1. No 115VAC to 24 VAC Trans-
former.
2. No 24VAC to Microboard.
3. Control Transformer defective,
no 24VAC output.
4. Short in wire to temp. sensors
or pressure transducers.
5. Defective IPU II & I/O Board or
the Display Board.
1a. Check wiring and fuse 1FU.
1b. Check wiring emergency stop
contacts 5 to L of XTBC2
Terminal Block.
1c. Replace Control Transformer.
2. Check wiring Control Trans-
former to Microboard.
3. Replace Control Transformer.
4. Unplug connections at IPU I &
I/O Board to isolate.
5. Replace IPU II & I/O Board or
the Display Board.
Contact Johnson Con-
trols Service before re-
placing Circuit Boards!
“FLOW SWITCH/REM STOP NO
RUN PERMISSIVE”
1. No air flow.
2. Air Proving Switch improperly
installed.
3. Defective Air Proving Switch.
4. Remote cycling device open.
1. Check air flow.
2 Check that the Air Proving
Switch is installed according to
manufacturer’s instructions.
3. Replace Air Proving Switch.
4. Check cycling devices connect-
ed to terminals 13 and 14 of the
XTBC1 Terminal Block.
Содержание YLUA0248 Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 65: ...JOHNSON CONTROLS 65 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13901 ...
Страница 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 71: ...JOHNSON CONTROLS 71 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13239 ...
Страница 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 75: ...JOHNSON CONTROLS 75 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13993A 1 ...
Страница 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...