SECTION 7 – UNIT CONTROLS
DISPLAY/PRINT KEYS
00067VIP
The Display/Print keys allow the user to retrieve sys-
tem and unit information that is useful for monitoring
unit operation, diagnosing potential problems, trouble-
shooting, and commissioning the unit.
System and unit information, unit options, setpoints,
and scheduling can also be printed out with the use of
a printer. Both real-time and history information are
available.
Oper Data Key
The OPER DATA key gives the user access to unit and
system operating parameters. When the OPER DATA
key is pressed, system parameters will be displayed and
remain on the display until another key is pressed. After
pressing the OPER DATA key, the various operating
data screens can be scrolled through by using the ↑ (UP)
and ↓ (DOWN) arrow keys or the ENTER/ADV key
located under the “ENTRY” section.
System 2 information will only be dis-
played for 2 system units.
With the “UNIT TYPE” set as a condensing unit (via
jumper between J11-7 and J11-12 on the I/O Board),
the following list of operating data screens are view-
able under the Oper Data key in the order that they are
displayed. The
↓
(DOWN) arrow key scrolls through
the displays in the order they appear below:
The unit MUST be set to be a condens-
ing unit via jumper between J11-7 and
J11-12 on the I/O Board. DO NOT
operate the unit if not properly set up.
D I S C H A R G E A I R T E M P
= 5 7 . 4 ° F
This display shows the discharge air temperature leav-
ing the evaporator. The display will only be shown
when the Control Mode is programmed for Discharge
Air (under the Options key). The minimum limit on
the display for these parameters are 9.2°F (-12.7°C).
The maximum limit on the display is 85.4°F (29.7°C).
A M B I E N T A I R T E M P
= 8 7 . 5 ° F
This display shows the ambient air temperature. The
minimum limit on the display is 0.4°F (-17.6°C). The
maximum limit on the display is 131.2°F (55.1°C).
Содержание YLUA0248 Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 65: ...JOHNSON CONTROLS 65 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13901 ...
Страница 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 71: ...JOHNSON CONTROLS 71 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13239 ...
Страница 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 75: ...JOHNSON CONTROLS 75 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13993A 1 ...
Страница 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...