SECTION 9 – SERVICE AND TROUBLESHOOTING
SERVICE MODE – CONDENSING UNIT
CONFIGURATION
After the Outputs are displayed, the next group of dis-
plays relate to unit configuration and start/hour coun-
ters. Data logging, soft start, refrigerant type, pump
control selection and expansion valve type all must be
programmed to match actual unit configuration.
Soft start (disabled), Refrigerant Type
(R410A), and Expansion Valve Type
(Thermostatic), and North American
Feature (Enabled) MUST be properly
programmed or damage to compressors
and other system components may result.
Following is a list of unit configuration selections, in
order of appearance:
HOT GAS BYPASS TYPE
UNIT TYPE (Standard or Heat Pump)
COMPRESSOR HOURS
COMPRESSOR STARTS
DATA LOGGING TIMER X SECS
FAN CONTROL TYPE (Single)
SOFT START (disabled)
REFRIGERANT TYPE (R410A only)
EXPANSION VALVE TYPE (Thermostatic Only)
REMOTE TEMP RESET OPTION =
REMOTE INPUT SERVICE TIME =
“NORTH AMERICAN FEATURE SET ENABLED”
HYDRO PUMP SELECTION
EVAP PUMP TOTAL RUN HOURS
SYS 1 HOURS
SYS 2 HOURS
SYS 1 STARTS
SYS 2 STARTS
The last displays shown on the above list are for the ac-
cumulated run and start timers for each system. All val-
ues can also be changed using the ↑ (UP) and ↓ (Down)
arrow keys, but under normal circumstances would not
be required or advised. After the last start display, the
micro will display the first programmable value under
the PROGRAM key.
SERVICE MODE – ANALOG AND DIGITAL
INPUTS
After entering Service Mode (PROGRAM
↑↑ ↓↓)
,
all digital and analog inputs to the microboard can be
viewed by pressing the OPER DATA key.
After pressing
the OPER DATA key, the ↑ (UP) arrow and ↓ (DOWN)
arrow keys are used to scroll through the analog and
digital inputs.
Following is the order of analog and digital inputs that
will appear when sequenced with the
↓ (
Down) arrow
key:
(analog inputs)
SYS 1 SUCT PRESSURE
UNIT TYPE
SYS 1 *DISCH PRESSURE
SYS 1** SUCTION TEMP.
SYS 2** SUCTION TEMP.
AMBIENT AIR TEMP.
LEAVING LIQUID TEMP.
RETURN LIQUID TEMP.
SYS 2 SUCTION PRESSURE
SYS 2 SPARE
SYS 2 *DISCH PRESSURE
SYS 1 MTR VOLTS
SYS 2 MTR VOLTS
(digital inputs)
PWM TEMP RESET INPUT
LOAD LIMIT INPUT
FLOW SW / REM START
SPARE
SINGLE SYSTEM SELECT
SYS 1 MP / HPCO INPUT
SYS 2 MP / HPCO INPUT
* The discharge pressure transducer is optional on some models.
** The suction temp. sensor is on EEV units only.
The analog inputs will display the input connection,
the temperature or pressure, and corresponding input
voltage such as:
S Y S 1 S U C T P R J 7 - 1 0
2 . 1 V D C = 8 1 P S I G
This example indicates that the system 1 suction pres-
sure input is connected to plug 7 – pin 10 (J7-10) on
the I/O board. It indicates that the voltage is 2.1 volts
dc which corresponds to 81 PSIG (5.6 bars) suction
pressure.
Содержание YLUA0248 Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 65: ...JOHNSON CONTROLS 65 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13901 ...
Страница 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 71: ...JOHNSON CONTROLS 71 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13239 ...
Страница 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 75: ...JOHNSON CONTROLS 75 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 LD13993A 1 ...
Страница 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Страница 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...