SECTION 6 – OPERATION
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
6
DATE AND TIME
After you press the
Date and Time
button, the Date
and Time screen displays. Use the following procedure
to make changes.
1. Press the
Change
button.
2. Enter the correct date and time.
3. Press the
Set
button to set the time.
4. Press the
Start
button to restart the clock.
If the clock is not keeping the correct time, use the fol-
lowing to fix it:
1. Press the
Correct
button to specify a correcting
amount (+ or -).
2. Press the
Set
button to update the time.
This calculated temperature is shown in Set Point as
the present target temperature. If remote set point set-
ting signal (4-20 mADC) is out of its range when you
press the
REMOTE
button, the
Recording Sensor
Abnormal Alarm
button lights. The target tempera-
ture changes to the Local setting.
See the figure below for more information.
LD20038
Setting
Base
Temp.
+
Remote
Setting
Diff.
Setting
Base
Temp.
4 mADC
Setpoint [°C]
Remote Setpoint Setting Signal
(4~20 mADC)
20 mADC
If a failure occurs, automatically move to the failure or
alarm screen.
For detailed information on how to change an entry
in one of these fields, see
VALVE OPERATION
Control Valve Mode:
Auto / Manual indicates wheth-
er the control valve is being operated automatically or
manually. To change to manual operation mode, press
and hold the
Manual
button for 3 seconds.
For detailed information on how to change the valve
position setting, see
Valve Position Setting:
shows the 3-way Valve Posi-
tion Setting, expressed as a percentage.
LD20029_UL
NOTE: When you enter the date informa-
tion, note that the format to use is: YYYY
/ MM / DD.
NOTE: To move to the Menu screen, set
the Control Valve Mode to Auto.
NOTE: The Valve Position Setting may be
changed ONLY when the Control Valve
Mode Manual button is pushed.
Содержание YHAU-CL Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...JOHNSON CONTROLS 47 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 128: ...JOHNSON CONTROLS 128 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...