Dry Storage Method
The dry storage method should be used if the chilled
water, cooling water, and/or the hot water system may
freeze in the winter or, if the chilled water, cooling wa-
ter, and/or hot water system has a lining tube. Do not
simply drain the chilled water, cooling water, and hot
water and store the machine. This significantly increas-
es the possibility of corrosion of the heat transfer tube
The dry storage procedure is as follows if the chilled
water, cooling water, and/or the hot water line is an
open system:
1. Completely drain the water.
2. Clean the water systems by passing clear water
through the tubes from a position higher than the
chiller.
3. Fill the water systems with clear water.
4. Circulate the clear water through the water pump
for 30 minutes to one hour to clean it.
5. Drain the water from each waterbox.
6. Dry the interior of each waterbox and the heat
transfer tube.
7. Store the machine.
PRECAUTIONS AGAINST EXTERNAL
DAMAGE
Avoid storing the machine in a place that is easily ac-
cessible or near a construction site. If this is unavoid-
able, provide the machine with protection.
If it is not possible to protect the machine, fill the in-
terior with N2 to minimize the amount of air leakage.
For details, contact your local Johnson Controls ser-
vice center.
Содержание YHAU-CL Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...JOHNSON CONTROLS 47 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 128: ...JOHNSON CONTROLS 128 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...