JOHNSON CONTROLS
160
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
SECTION 8 – TROUBLESHOOTING
VACUUM PUMP
When the
Purge Abnormal
button lights on the Fail-
ure and Alarm screen, the vacuum pump needs to be
disassembled for inspection. Contact your local John-
son Controls Service Center. The entire purge line must
be inspected if the
Abnormal Purge Freq.
button on
the same screen lights, or if the vacuum level of the
purge line does not reach the specified level during the
vacuum pump capacity check.
TABLE 45 -
VACUUM PUMP TROUBLESHOOTING
ITEM
CAUSE
COUNTERMEASURE
1
Deterioration of vacuum pump oil
Replace the vacuum pump oil.
2
Wrong operation of purging line switching when
vacuum pump capacity was checked
open or closed.
3
Deterioration of vacuum pump belt
Contact your local Johnson Controls Service Center.
4
Leakage in purge pipe lines
5
Solenoid valve or check valve in the purge line is
clogged
Содержание YHAU-CL Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...JOHNSON CONTROLS 47 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 128: ...JOHNSON CONTROLS 128 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...