SECTION 4 - TECHNICAL DATA
TABLE 14 -
CONTACT SPECIFICATIONS
CONTACT SPECIFICATION
Absorption Chiller Control Panel - External
Output Terminal
Digital Signal
Max. Open/Close Voltage: AC250 V/DC30 V
Max. Open/Close Current: 2A/1 Point (Resistance Load)
Max. Common Current: 8 A (Resistance Load)
Analog Signal
Allowed Resistance Load: 550 Ohm
External - Absorption Chiller Control Panel
Digital Signal
Rating Voltage/Current: DC24 V/7 m A
LD20545
STARTING PANEL FOR CHILLED WATER
STARTING PANEL FOR CHILLER WATER
Example diagram of transition wiring if start panel of
chilled water pump and cooling water pump are
separately equipped.
Z1 TERMINAL BLOCK
COMMON
OPERATING SIGNAL
CHILLING WATER PUMP OPERATING SIGNAL
FAILURE SIGNAL
COOLING WATER PUMP OPERATING SIGNAL
INTERLOCK
TEST
INTERLOCK
TEST
FIGURE 35 -
SIGNAL TERMINAL TRANSITION WIRING
Содержание YHAU-CL Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...JOHNSON CONTROLS 47 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 128: ...JOHNSON CONTROLS 128 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...